User manual

Magelis A - 15
1. XBT N/XBT R display units
A
Characteristics
Type of display unit XBT-N200 XBT-N400 XBT NU400 XBT-N401
Environment
Conformity to standards IEC 61131-2, IEC 60068-2-6, IEC 60068-2-27, UL 508, CSA C22-2 no. 14
Product certification CE, UL, CSA, Class 1 Div 2 T5 (UL and CSA)
Temperature Operation 0 … +55°C (32°F … 131°F)
Storage -20 … +60°C (-4°F … 140°F)
Relative humidity 0 … 85% (without condensation)
Degree of
protection
Front panel IP 65, according to IEC 60529, UL Type 4, 4X
Rear panel IP 20, according to IEC 60529
Shock resistance According to IEC 60068-2-27; semi-sinusoidal impulse 11 ms, 15 g on 3 axes
Vibrations
According to IEC 60068-2-6, 10 to 57 Hz at 0.075 mm; 57 to 150 Hz 1 g for 3 hours per
axis
E.S.D. According to IEC 61000-4-2, level 3
Electromagnetic interference According to IEC 61000-4-3, 10 V/m
Electrical interference According to IEC 61000-4-4, level 3
Mechanical characteristics
Mounting and fixing
Flush-mounted, fixed by 2 spring clips supplied pressure-mounted for panels 1.5 to 6
mm thick
Material Screen protection Polyester
Front frame Polycarbonate/polybutylene terephthalate alloy
Keypad UV autotex polyester
Electrical characteristics
Power supply Voltage 5 V DC via the serial link with the PLC 24 V DC (200 mA max)
Voltage limits 18 . . . 30 V DC
Ripple factor 5% maximum
Operating characteristics
Display unit Type Backlit LCD
Capacity 2 x 20 characters From 4 x 20 to 1 x 5 characters (large size)
Signaling No LEDs 6 LEDs
Dialog
application
No. of pages 128 200
Transmission medium
(asynchronous serial link)
RS232/RS485
Downloadable protocols Modbus master, Uni-Telway Modbus master
Modbus master and
slave, Uni-Telway
Real-time clock Access to the PLC real-time clock
Connection Power supply Via the PLC link cable
Removable terminal block
3 screw terminals (pitch 5.08)
Clamping capacity: 1.5 mm2
Serial link RJ45 female connector (RS232/RS485) 25-pin female SubD connector
Printer link No printer link MiniDin