User manual
A - 12 Magelis
1. XBT N/XBT R display units
Magelis-PLC link: Running
XBT N200/N400
XBT R400
Twido/Micro
Premium/Nano
Power supply mode: powered by the PLC
Depending on which protocol is used, if "?????" is displayed rather
than any values, or the connection popup remains on screen, this
indicates a communication problem. This may originate from the
cable being used. To resolve this problem, use the XBT Z9780 cable
fitted with the XBT ZN999 adaptor (for more information, see
chapter E, section 1. Troubleshooting/Problems and solutions, Page
5).
XBT front panel Cable
Without the Telemecanique logo
XBT L1000 version ≤ V4.30 +
XBT Z978 cable
XBT L1000 version ≥ V4.40 +
XBT Z9780 cable +
XBT ZN999 adaptor
With the Telemecanique logo
XBT L1000 version ≥ V4.40 +
XBT Z9780 cable
RJ45 connector compatibility table