7. Description of dialog-table words
How the various bytes are entered can be selected in the XBT L100•
configuration software: Either BCD format (in which case if it is fifteen
hours, the content of the Hour field will be 0x15) or Standard format (in
which case if it is fifteen hours, the content of the Hour field will be 0x0F)
can be selected.
The choice of BCD/Standard applies to all these four words, and cannot
be made independently for each byte. The “Day of the week” field is not
used by the display unit: The latter automatically calculates the right day
associated with a given date. Irrespective of the content of the
“Day of the week” field, the display unit ignores it.