User manual
Magelis C - 85
7. Description of dialog-table words
C
Depending on the type of display unit, more or fewer alarms may be
permitted. Nevertheless, the structure of a word used to signal alarms is
always as follows: One 16-bit word, where each bit represents an alarm.
When several alarm words are positioned in a device, the alarms are
numbered bit by bit, starting with the least-significant bit in the lowest
order address (bearing the number 1) and ascending towards the
most-significant bit and the highest-order address:
When several alarm words are defined in a given device, these words
are always located in consecutive addresses: There cannot be a gap
between alarm numbers.
Set terminal clock
This set of 16-bit words, each divided into 2 bytes, enables the control
system to update the display unit real-time clock.
XBT <- PLC Alarm
No.
of bit
F E D C B A 9 8
Alarm
Page
No.
#16 #15 #14 #13 #12 #11 #10 #9
#32 #31 #30 #29 #28 #27 #26 #25
... ... ... ... ... ... ... ...
#256 #255 #254 #253 #252 #251 #250 #249
No.
of bit
7 6 5 4 3 2 1 0
Alarm
Page
No.
#8 #7 #6 #5 #4 #3 #2 #1
#24 #23 #22 #21 #20 #19 #18 #17
... ... ... ... ... ... ... ...
#248 #247 #246 #245 #244 #243 #242 #241
XBT <- PLC Seconds Day of the week
XBT <- PLC Hours Minutes
XBT <- PLC Month Day
XBT <- PLC Century Year
XBT ref. Note
//