User manual
Magelis C - 73
7. Description of dialog-table words
C
Terminal advanced state
This word is used split into two bytes, the first of which is reserved and
the second used bit by bit.
Current password level
:
These three least-significant bits (0 to 2) in the lower byte contain
information relating to the current display-unit password. Each bit is at 1
if the associated password is selected, and each bit is at 0 if the
associated password is not selected.
The advantage of this word is as follows: It enables the display-unit
password to be used as the password for the PLC (enabling, for
example, the whole process to be switched to a certain state, for
example maintenance, by means of the display unit, by entering the ad
hoc password: The display unit can then access pages shared by a
maintenance password, and the PLC can thus know that the display unit
is in maintenance mode, enabling it in turn to switch to a mode where it
is ready to accept modifications).
It should be noted that for reasons of compatibility with existing PLC
applications, there is also a bit in the "Report" word (the
CONFIDENTIAL_MODE bit), which is at 1 as soon as at least one
password has been confirmed.
XBT -> PLC Reserved equals 000000CBA
Bit 15 8 7 2 1 0
XBT -> PLC Report
Bit 15 0
XBT ref. Note
//