User manual

C - 70 Magelis
7. Description of dialog-table words
Note that to simplify time-setting management in the pilot equipment, a
status-word bit is assigned to this function.
Bit 13 changes to 1 in cases where the operator updates the time on the
terminal.
Number of page displayed
This word contains the number of the page displayed on the terminal.
The code of the page displayed follows the same rules as those which
apply to the "Number of page to be processed" word, and in addition the
following rule exists: the "Number of page displayed" word equals
0xFFFF in the following cases:
- When the display unit displays an alarm
(1)
- When the display unit is in the processing of changing page
Recommended method of displaying a page (see chapter C,
section Number of page to be processed, Page 74)
Number of last completed field
This word contains the number of the last completed field. A field is
considered to have been completed when it has been confirmed with
, or as soon as the associated PLC value has been modified by the
user (as is the case when the field is in immediate-write mode). The field
number is available in XBT L100•, via the Display/Field Numbers
menu.
Recommended method of displaying a page (see section Number of
field to be completed, Page 75)
XBT -> PLC
Report
Bit 15 13 0
XBT -> PLC Number of page displayed
XBT -> PLC Number of last completed field
XBT ref. Note
N200
(1) No alarm management