User manual
Connecting XBT Terminals
74
33003962 11/2011
Communication Interruption with XBT N200 or XBT N400 Terminals
A communication interruption may have occurred if ????? is displayed rather than
any values, or the connection popup remains on the display unit. If you are using an
XBT N200 or an XBT N400 terminal, it may be caused by the cabling because
different cables are required for the different terminal versions. Use the cables as
shown in the table below. If you are using other terminals or the condition still
persists with these cable, refer to section Troubleshooting, page 156 or to the
manual describing the protocol you are using for more information.
RJ45 connector compatibility table
XBT N Front Panel Cable
Without Telemecanique or Schneider Electric
logo
XBT Z978
XBT Z9780 + XBT ZN999 adaptor
Application example: XBT N without Telemecanique logo
connected via XBT Z9780 cable and XBT ZN999 adaptor
With Telemecanique or Schneider Electric logo XBT Z9780