User manual

Magelis XBT OT User Manual
3-12
3.2 XBT OT4320 Series
3.2.1 General Specifications
Electrical Specifications
Environmental Specifications
Power Supply
Input Voltage 24 VDC
Rated Voltage 19.2 to 28.8 VDC
Allowable Voltage Drop 10ms (max.)
Power Consumption 22W (max.)
In-Rush Current 30A (max.)
Voltage Endurance
1000 VAC 20mA for 1 minute
(between charging and FG terminals)
Insulation Resistance
500 VDC 10MΩ (min.)
(between charging and FG terminals)
Physical
Surrounding Air
Temperature
0 to +50°C [32 to 122°F]
Storage Temperature -20 to +60°C [-4 to 140°F]
Ambient Humidity
10 to 90% RH
(Wet bulb temperature: 39°C[102°F] max. - no condensation.)
Storage Humidity
10 to 90% RH
(Wet bulb temperature: 39°C[102°F] max. - no condensation.)
Dust 0.1mg/m
3
and below (non-conductive levels)
Pollution Degree For use in Pollution Degree 2 environment
Atmosphere Free of corrosive gases
Air Pressure Vibration
Resistance
800 to 1114hPa
(2,000m[6557.4ft] above sea-level and below)
Mechanical
Vibration Resistance
IEC61131-2 compliant
5 to 9Hz single-amplitude 3.5mm[0.14in]
9 to 150Hz constant acceleration 9.8m/s
2
X,Y,Z directions for 10 cycle (100 minute)
Concussion Resistance
IEC61131-2 compliant
(147m/s
2
X,Y,Z directions for 3 times)
Electrical
Noise Immunity
Noise Voltage: 1000V
P-P
Pulse Duration: 1μs
Rise Time: 1ns
(via noise simulator)
Electrostatic Discharge
Immunity
6kV (complies with EN 61000-4-2 Level 3)