Thank you for purchasing one of Schneider’s OPTI XBT OT Series Programmable Operator Interface modules (hereafter referred to as the “OT unit”). Before operating your OT unit, be sure to read this manual to familiarize yourself with the OT unit’s operation procedures and features. NOTICE 1. Copying this manual’s contents, either in whole or in part, is prohibited without the express permission of Schneider Electric. 2. The information contained in this manual is subject to change without notice. 3.
Contents Safety Instructions..................................................................................................... 3 Information Symbols.................................................................................................. 4 Handling the LCD Panel............................................................................................ 5 XBT OT Series Models and Features ....................................................................... 6 Package Contents ..................
Chapter 4 Installation and Wiring 4.1 Installation....................................................................................................... 4-2 4.2 Wiring Precautions.......................................................................................... 4-7 4.2.1 Connecting the Power Cord..................................................................................4-7 4.2.2 Connecting the Power Supply.............................................................................4-12 4.2.
Safety Instructions Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
Information Symbols This manual uses the following icons: Screen Editor Indicates the Vijeo Designer software. PLC Abbreviation for Programmable Logic Controller. Indicates useful or important supplemental information. Contains additional or useful information. SEE 4 Indicates pages containing related information.
Handling the LCD Panel The following characteristics are specific to the LCD unit and are considered normal behavior: • LCD screen may show unevenness in the brightness of certain images or may appear different when seen from outside the specified viewing angle. Extended shadows, or crosstalk may also appear on the sides of screen images. • LCD screen pixels may contain black and white colored spots and color display may seem to have changed.
XBT OT Series Models and Features The XBT OT series refers to the following model numbers: Model XBT OT2110 XBT OT2210 XBT OT4320 XBT OT5220 XBT OT5320 CPU LH7A404 LH7A404 LH7A404 LH7A404 LH7A404 OS VxWorks VxWorks VxWorks VxWorks VxWorks DRAM 32MB 32MB 32MB 32MB 32MB Main Flash 32MB 32MB 32MB 32MB 32MB SRAM 512K 512K 512K 512K 512K Panel Size 5.7” 5.7” 7.5” 10.4” 10.
WARNING LOSS OF CONTROL • The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop. • Separate or redundant control paths must be provided for critical control functions. • System control paths may include communication links.
Package Contents The following items are included in the OT unit’s package. Before using the OT, please check that items listed are present.
UL/c-UL Approval The following units are UL/c-UL listed products. (UL File No.E220851) Product Model No. UL/c-UL Registration Model No. XBT OT2110 3580207-02 XBT OT2210 3580207-01 XBT OT4320 3580206-01 XBT OT5220 3520208-02 XBT OT5320 3520208-02 This product conforms to the following standards: • UL508 Industrial Control Equipment • CSA-C22.2 No.142-M1987 (c-UL Approval) Standard for Process Control Equipment CAUTION EQUIPMENT DAMAGE • The OT unit's rear face is not approved as an enclosure.
CE Marking The following units are CE marked products complying with the EMC Directive. They comply with EN55011 Class A, EN61131-2.
1 Overview 1. System Design 2. Accessories This chapter describes the peripheral devices that can be connected to the OT Series units.
Magelis XBT OT User Manual 1.1 System Design The following diagram illustrates the standard range of items that can be connected to XBT OT Series units. For host controller (PLC, etc.) connection information, refer to the Vijeo Designer Online Help’s Device Driver manuals. OT RUN Mode Peripherals For explanation of numbered items, see Component Legend on Page 1-4.
Chapter 1 Overview (3) (5) RS-232C Cable XBTZG9731 RS-232C Isolation Unit XBTZGI232 (5) Switch setting: RS-232C Mitsubishi PLC Q-Series Link Cable XBTZG9772 (5) Host Controller PLC etc.
Magelis XBT OT User Manual (4) Mitsubishi PLC FX-Series Connection Cable XBTZG9775 (8) Mitsubishi PLC A-Series Connection Cable XBTZG9773 (8) (6) Host Controller PLC etc.
Chapter 1 Overview Editor Peripherals OT Unit (1) USB Port USB Transfer Cable XBTZG935 (2) PCMCIA Slot CF Card XBTZGM128 XBTZGM256 MPCYN00CFE00N MPCYN00CF100N CF Card Adapter XBTZGADT Personal Computer (Commercial type) *3 *3 Vijeo-Designer Screen Editor Software Certain types and models of PCs cannot be used.
Magelis XBT OT User Manual 1.2 Accessories All accessories listed here are produced by Schneider Electric. Serial Interface Item 1-6 Product Name Model No. Description RS-232C Cable XBTZG9731 (5m[16.4ft]) Connects Mitsubishi PLC A-Series (or other host controller) to the OT. (RS-232C) RS-422 Cable XBTZG9722 (5m[16.4ft]) Connects a host controller to the OT. (RS-422) Mitsubishi PLC Q-Series Link Cable XBTZG9775 (5m[16.
Chapter 1 Overview USB Host Interface Product Name Model No. Description USB Transfer Cable XBTZG935 (2m[3.3ft]) Downloads project data created with the Screen Editor via the OT unit’s Serial I/F. USB Front Cable XBTZGUSB (1m[3.3ft]) Extension cable attaching USB port to front panel. CF Card Items Only the XBT OT4320/5220/5320 Series includes an interface to the CF Cards. Product Name Model No.
Magelis XBT OT User Manual 1-8
2 Part Names and Functions 1. XBT OT2110/2210 Series 2. XBT OT4320 Series 3. XBT OT5220/5320 Series This chapter describes the names and functions of the components of the OT series.
Magelis XBT OT User Manual 2.1 XBT OT2110/2210 Series A: Status LED This LED indicates the OT’s status, e.g. power input, firmware RUN status. LED A Front OT Operation Green (lit) Normal operation (power is ON) or OFFLINE operation. Orange (blinking) During software startup. Red (lit) Power is ON. Not lit Power is OFF. B: Power Plug Connector C C: USB Host Interface (USB) D Complies with USB 1.1. One port for TYPE-A connector. B E Power supply voltage 5 VDC ±5%.
Chapter 2 Part Names and Functions 2.2 XBT OT4320 Series A: Status LED This LED indicates the OT’s status, e.g. power input, firmware RUN status. LED A Front OT Operation Green (lit) Normal operation (power is ON) or OFFLINE operation. Orange (blinking) During software startup. Red (lit) Power is ON. Not lit Power is OFF. B: CF Card Access Lamp This lamp lights up when a CF Card is inserted and the CF Card cover is closed.
Magelis XBT OT User Manual F G H Bottom (With CF Card Cover open) F: USB Host Interface (USB) Complies with USB 1.1. One port for TYPE-A connector. Power supply voltage 5 VDC ±5%. Maximum output current: 500mA Maximum communication distance: 5m[16.4ft] Interfaces to transfer cable, USB-compatible printer, and such. G: CF Card Cover The CF Card interface and DIP Switches are located inside the CF Card access area when the cover is open. This cover must be closed when accessing the CF Card.
Chapter 2 Part Names and Functions 2.3 XBT OT5220/5320 Series A: Status LED This LED indicates the OT’s status, e.g. power input, firmware RUN status. LED A Front C E H Green (lit) Normal operation (power is ON) or OFFLINE operation. Orange (blinking) During software startup. Red (lit) When power is turned ON. Not lit Power is OFF. B: USB Host Interface (USB) Complies with USB 1.1. One port for the TYPE-A Connector. Power supply voltage 5 VDC ±5%.
Magelis XBT OT User Manual H: DIP Switches ON 1 2 3 4 DIP Switches ON OFF Install project from CF Card. CF Card with project data required. Default setting: OFF. Enabled Disabled 1 2 Reserved - - Enable Runtime Recovery. Default setting: OFF. Enabled, contact customer support for serial recovery cable Disabled 3 Simulate cover closed, allowing card to be read even if cover open. Default setting: OFF.
3 Specifications 1. XBT OT2110/2210 Series 2. XBT OT4320 Series 3. XBT OT5220/5320 Series This chapter describes the general specifications, functions, interfaces and dimensions of the OT.
Magelis XBT OT User Manual 3.1 XBT OT2110/2210 Series 3.1.1 General Specifications Power Supply Electrical Specifications Input Voltage 24 VDC Rated Voltage 19.2 to 28.8 VDC Allowable Voltage Drop 10ms (maximum) Power Consumption 18W (maximum) In-Rush Current 30A (max.) Voltage Endurance 1000 VAC 20mA for 1 minute (between charging and FG terminals) Insulation Resistance 500 VAC 10MΩ (min.
Chapter 3 Specifications Installation Structural Specifications Grounding Grounding resistance of 100Ω 2mm2 or thicker wire, or your country’s applicable standard. (Same for FG and SG terminals) *1 Structure Rating: Equivalent to IP65f NEMA #250 TYPE 4X/13 (Front surface at panel embedding) Feature size: All-in-one Installation configuration: Panel embedding Cooling Method Natural air circulation Weight Approx. 1.0kg[2.2lb]max. (unit only) External Dimensions W167.5mm[6.59in] X H135mm[5.
Magelis XBT OT User Manual 3.1.2 Performance Specifications Performance Specifications Application*1 FLASH EPROM 32MB SRAM 512KB Data Backup Used lithium battery for backup memory Interface COM1: RS-232C Asynchronous Transmission Data Length: 7 bit/8 bit Parity: none, Odd or Even Stop Bit: 1bit/2bit Data transmission Speed: 2400bps to 115.
Chapter 3 Specifications Display Specifications Display Type XBT OT2210 XBT OT2110 STN Color LCD Monochrome blue mode LCD W320 X H240 pixels Dot pitch W0.36mm[0.01in] X H0.36mm[0.01in] Effective Display Area W115.2mm[4.54in] X H86.4mm[3.40in] Color/Shade level 256 Colors (No blink) 64 Colors (Enables blink feature) Backlight CCFL (Not replaceable.
Magelis XBT OT User Manual 3.1.3 Interface Specifications This section describes the specifications of each interface of the OT Series unit. DANGER ELECTRIC SHOCK • The OT unit’s serial port is not isolated. When the host (PLC) unit is also not isolated, be sure to connect the #5 SG (Signal Ground) terminal to reduce the risk of damaging the RS-232C/ RS-422 circuit.
Chapter 3 Specifications Serial Interfaces Serial Interface (COM1) This interface is used to connect an RS-232C serial cable. A 9-pin SUB-D plug connector is used. OT unit side OT Connector XM2C-0942-502LX (OMRON Co.) Interfit Bracket #4-40 inch screws are used. Cable side Recommended Cable Connector XM2D-0901 (OMRON Co.) Recommended Cable Cover XM2S-0913 (OMRON Co.) Recommended Jack Screw XM2Z-0073 (OMRON Co.) RS-232C Pin Arrangement Pin No.
Magelis XBT OT User Manual Serial Interface (COM2) This interface is used to connect an RS-422/485 serial cable. A 9-pin SUB-D plug connector is used. OT unit side OT Connector XM2C-0942-502LX (OMRON Co.) Interfit Bracket #4-40 inch screws are used. Cable side Recommended Cable Connector XM2D-0901 (OMRON Co.) Recommended Cable Cover XM2S-0913 (OMRON Co.) Recommended Jack Screw XM2Z-0073 (OMRON Co.) RS-422/485 Pin Arrangement 5 9 1 6 (OT unit side) 3-8 Pin No.
Chapter 3 Specifications Dimensions The following dimensions apply to the XBT OT2110/2210 models. Installation Fasteners Attached Dimensions Unit: mm[in.] 155.5[6.12] 65[2.56] 65[2.56] Top Left side 134.4[5.29] 135[5.31] Front 59.5[2.34] 123[4.84] 5[0.20] 167.5[6.59] 144.4[5.69] 3.1.4 Right side 50 50 [1.97] [1.
Magelis XBT OT User Manual Cable Attached Dimensions Unit:mm[in.] 96[3.78] 123[4.84] Left side Rear Right side Bottom • Depending on the type of connection cable used the dimensions shown above will change. The dimensions given here are representative values and are intended for reference only.
Chapter 3 Specifications Panel Cut Dimensions Unit: mm[in.] +1 -0 [6.14 +0.04 ] -0 Under 4-R3[0.12] +1 +0.04 [4.86 ] -0 -0 156 123.5 Panel thickness area 1.6[0.06] to 5.0[0.20] Installation Fasteners Unit: mm[in.] 11 [0.43] 16[0.63] 16.6[0.65] 31[1.22] ∅10[0.
Magelis XBT OT User Manual 3.2 XBT OT4320 Series 3.2.1 General Specifications Power Supply Electrical Specifications Input Voltage 24 VDC Rated Voltage 19.2 to 28.8 VDC Allowable Voltage Drop 10ms (max.) Power Consumption 22W (max.) In-Rush Current 30A (max.) Voltage Endurance 1000 VAC 20mA for 1 minute (between charging and FG terminals) Insulation Resistance 500 VDC 10MΩ (min.
Chapter 3 Specifications Installation Structural Specifications Grounding Grounding resistance of 100Ω 2mm2 or thicker wire, or your country’s applicable standard. (Same for FG and SG terminals) *1 Structure Rating: Equivalent to IP65f NEMA #250 TYPE 4X/13 (Front surface at panel embedding) Feature size: All-in-one Installation configuration: Panel embedding Cooling Method Natural air circulation Weight Approx. 1.8kg[4lb]max. (unit only) External Dimensions W215mm[8.47in] X H170mm[6.
Magelis XBT OT User Manual 3.2.2 Performance Specifications Performance Specifications Application*1 FLASH EPROM 32MB SRAM 512KB Data Backup Used lithium battery for backup memory Interface COM1: RS-232C Asynchronous Transmission Data Length: 7 bit/8 bit Parity: none, Odd or Even Stop Bit: 1bit/2bit Data transmission Speed: 2400bps to 115.
Chapter 3 Specifications Display Specifications Display Type Resolution Dot pitch Effective Display Area Color/Shade level Backlight Brightness control Contrast Adjustment Display Service Life Backlight Service Life Text Text composition Language Fonts TFT Color LCD W640 X H480 pixels W0.237mm[0.01in] X H0.237mm[0.01in] W151.68mm[5.97in] X H113.76mm[4.48in] 256 Colors (No blink) 64 Colors (Enables blink feature) CCFL (Not replaceable.
Magelis XBT OT User Manual 3.2.3 Interface Specifications This section describes the specifications of each interface of the OT Series unit. DANGER ELECTRIC SHOCK • The OT unit’s serial port is not isolated. When the host (PLC) unit is also not isolated, be sure to connect the #5 SG (Signal Ground) terminal to reduce the risk of damaging the RS-232C/ RS-422 circuit.
Chapter 3 Specifications Serial Interfaces Serial Interface (COM1) This interface is used to connect an RS-232C serial cable. A 9-pin SUB-D plug connector is used. OT unit side OT Connector XM2C-0942-502LX (OMRON Co.) Interfit Bracket #4-40 inch screws are used. Cable side Recommended Cable Connector XM2D-0901 (OMRON Co.) Recommended Cable Cover XM2S-0913 (OMRON Co.) Recommended Jack Screw XM2Z-0073 (OMRON Co.) RS-232C Pin Arrangement Pin No.
Magelis XBT OT User Manual Serial Interface (COM2) This interface is used to connect an RS-422/485 serial cable. A 9-pin SUB-D plug connector is used. OT unit side OT Connector XM2C-0942-502LX (OMRON Co.) Interfit Bracket #4-40 inch screws are used. Cable side Recommended Cable Connector XM2D-0901 (OMRON Co.) Recommended Cable Cover XM2S-0913 (OMRON Co.) Recommended Jack Screw XM2Z-0073 (OMRON Co.) RS-422/485 Pin Arrangement Pin No.
Chapter 3 Specifications Dimensions The following dimensions apply to the XBT OT4320 models. Installation Fasteners Attached Dimensions Unit: mm[in.] 204[8.03] 83[3.27] 83[3.27] Top 215[8.47] 60[2.36] Left side 159[6.26] 170[6.69] Front 170.4[6.71] 5[0.20] 180.4[7.10] 3.2.4 Right side 83[3.27] 83[3.
Magelis XBT OT User Manual Cable Attached Dimensions Unit:mm[in.] 147.9[5.82] 133.7[5.26] 134[5.28] Left side Rear Right side Bottom • Depending on the type of connection cable used the dimensions shown above will change. The dimensions given here are representative values and are intended for reference only.
Chapter 3 Specifications Panel Cut Dimensions Unit: mm[in.] 204.5 +1 [8.05 +0.04 ] -0 -0 +1 +0.04 159.5 -0 [6.28 -0 ] Under 4-R3[0.12] Panel thickness area 1.6[0.06] to 10.0[0.39] Installation Fasteners Unit: mm[in.] 11[0.43] 16[0.63] 16.6[0.65] 31[1.22] ∅10[0.
Magelis XBT OT User Manual 3.3 XBT OT5220/5320 Series 3.3.1 General Specifications Electrical Specifications Power Supply Input Voltage 24 VDC Rated Voltage 19.2 to 28.8 VDC Rated frequency - Rated frequency range - Allowable Voltage Drop 10ms or less Power Consumption 45W or less In-Rush Current 30A or less Voltage Endurance 1000 VAC 20mA 1minute Insulation Resistance 500 VDC 10MΩ (min.
Chapter 3 Specifications Structural Specifications Grounding Structure Rating: Equivalent to IP65f NEMA #250 TYPE 4X/13 (Front surface at panel embedding) Feature size: All-in-one Installation configuration: Panel embedding Cooling Method Natural air circulation Weight Approx. 2.5kg[5.5lb] max. (unit only) External Dimensions W270.5mm[10.65in] X H212.5mm[8.37in] X D57mm[2.24in] Panel Cut Dimensions W259mm[10.20in] X H201mm[7.91in]*2 Panel thickness: 1.6mm[0.06in] to 10.0mm[0.
Magelis XBT OT User Manual 3.3.2 Performance Specifications Performance Specifications Application*1 Data Backup Interface Serial Interface FLASH EPROM 32MB SRAM 512KB Used lithium battery for backup memory COM1: RS-232C Asynchronous Transmission Data Length: 7 bit/8 bit Parity: none, Odd or Even Stop Bit: 1bit/2bit Data transmission Speed: 2400bps to 115.
Chapter 3 Specifications Display Specifications Display Type XBT OT5220 XBT OT5320 Color LCD TFT Color LCD W640 X H480 pixels Dot pitch W0.33mm[0.01in] X H0.33mm[0.01in] Effective Display Area W211.2mm[8.31in] X H158.4mm[6.24in] Color/Shade level 16 Colors Backlight CCFL (Not replaceable) Brightness control 8 levels of adjustment available via touch panel Contrast Adjustment Not applicable Display Service Life MTBF value: 50,000hrs.
Magelis XBT OT User Manual 3.3.3 Interface Specifications This section describes the specifications of each interface of the OT Series unit. DANGER ELECTRIC SHOCK • The OT unit’s serial port is not isolated. When the host (PLC) unit is also not isolated, be sure to connect the #5 SG (Signal Ground) terminal to reduce the risk of damaging the RS-232C/ RS-422 circuit.
Chapter 3 Specifications Serial Interfaces Serial Interface (COM1) This interface is used to connect an RS-232C serial cable. A 9-pin SUB-D plug connector is used. OT unit side OT Connector XM2C-0942-502L (OMRON Co.) Interfit Bracket #4-40 inch screws are used. Cable side Recommended Cable Connector XM2D-0901 (OMRON Co.) Recommended Cable Cover XM2S-0913 (OMRON Co.) Recommended Jack Screw XM2Z-0073 (OMRON Co.) RS-232C Pin Arrangement 5 9 1 6 (OT unit side) *1 Pin No.
Magelis XBT OT User Manual Serial Interface (COM2) This interface is used to connect an RS-422/485 serial cable. A 9-pin SUB-D plug connector is used. OT unit side OT Connector XM2C-0942-502LX (OMRON Co.) Interfit Bracket #4-40 inch screws are used. Cable side Recommended Cable Connector XM2D-0901 (OMRON Co.) Recommended Cable Cover XM2S-0913 (OMRON Co.) Recommended Jack Screw XM2Z-0073 (OMRON Co.) RS-422/485 Pin Arrangement Pin No.
Chapter 3 Specifications Dimensions The following dimensions apply to the XBT OT5220/5320 models. Installation Fasteners Attached Dimensions Unit: mm[in.] 258.5[10.18] 110[4.33] 110[4.33] Top 57[2.24] 270.5[10.65] Left side 212.5[8.37] Right side Front 110[4.33] 200.5[7.89] 5[0.20] 212.5[8.37] 222.5[8.76] 3.3.4 110[4.
Magelis XBT OT User Manual Cable Attached Dimensions Left side 141[5.55] 130[5.12] Unit:mm[in.] Rear Right side Power Connector Bottom 60.4 [2.38] The DC model unit has the power supply terminals shown above. • Depending on the type of connection cable used the dimensions shown above will change. The dimensions given here are representative values and are intended for reference only.
Chapter 3 Specifications Panel Cut Dimensions Unit: mm[in.] +1 +0.04 [10.20 ] -0 -0 Under 4-R3[0.12] Panel thickness area 1.6[0.06] to 10.0[0.39] 201 +1 +0.04 [7.91 ] -0 -0 259 Installation Fasteners Unit: mm[in.] 11 [0.43] 16[0.63] 16.6[0.65] 31[1.22] ∅10[0.
Magelis XBT OT User Manual 3-32
4 Installation and Wiring 1. Installation 2. Wiring Precautions 3. CF Card Insertion/Removal 4. USB Cable Clamp Attachment/Removal This chapter describes the installation and cable arrangement of the OT Series and its peripheral equipment.
Magelis XBT OT User Manual 4.1 Installation This section describes the procedures and precautions for installing the OT Series units. Check the Installation Gasket’s Seating It is strongly recommended that you use the installation gasket, since it absorbs vibration in addition to repelling water. SEE 5.3 Replacing the Installation Gasket (page 5-3) for the procedure for attaching the installation gasket.
Chapter 4 Installation and Wiring Installation Requirement • For easier maintenance, operation, and improved ventilation, be sure to install the OT at least 100mm [3.94in] away from adjacent structures and other equipment. Unit: mm[in.] 100 [3.94] 100 [3.94] 100 [3.94] 100 [3.94] 100 [3.94] • 100 [3.94] 100 [3.94] Be sure that the ambient operation temperature and the ambient humidity are within their designated ranges.
Magelis XBT OT User Manual • When installing the OT in a slanted panel, the panel face should not incline more than 30°. 30° or less • When installing the OT in a slanted panel, and the panel face inclines more than 30°, the ambient temperature must not exceed 40°C[104°F]. You may need to use forced air cooling (fan, A/C) to ensure the ambient operating temperature is 40°C[104°F] or below.
Chapter 4 Installation and Wiring Installing the OT (1) Insert the OT into the panel cut, as shown. (2) Mount four pieces of the panel-mounting Installation Panel brackets on the right and left sides, or the top and bottom sides of the panel to secure the panel.
Magelis XBT OT User Manual (3) Insert each of the fasteners shown below. Be sure to pull the fastener back until it is flush with the rear of the attachment hole. (4) Use a Phillips screwdriver to tighten each fastener screw and secure the OT in place. • Tightening the screws with too much force can damage the OT unit’s plastic case. • The torque required to tighten these screws is 0.5 N.m(4.4 lb-in).
Chapter 4 Installation and Wiring 4.2 Wiring Precautions This section describes the procedures and precautions for wiring power cords. 4.2.1 Connecting the Power Cord WARNING POWER, WIRING, AND GROUNDING HAZARDS • Be sure the 24 VDC power is OFF when wiring to the power terminals of the unit. • The unit uses only 24 VDC power. Using any other level of power can damage both the power supply and the unit.
Magelis XBT OT User Manual Power Connector (Plug) Specifications XBT OT2110/2210/4320 Series + 24V - 0V FG FG Grounding Terminal connected to the OT + 24V - 0V FG FG Grounding Terminal connected to the OT Insertion Direction + − FG XBT OT5220/5320 Series FG − + Power Cord Insertion Holes Wiring When connecting the Power Cord, use the following items when performing wiring. (Items are made by Phoenix Contact.) 4-8 Recommended Driver SZF 1-0.6x3.
Chapter 4 Installation and Wiring Connecting the Power Cord WARNING POWER LOSS • Remove the connector from the OT unit prior to starting wiring. • Avoid excessive stress on the power cable to prevent accidental disconnection. • Securely attach power cables to the panel or cabinet. • Use the designated torque to tighten the unit’s terminal block screws. • Install and fasten unit on installation panel or cabinet prior to connecting Power Supply and Communication lines.
Magelis XBT OT User Manual XBT OT5220/5320 Series (1) Confirm that the power cord is unplugged from the power supply. (2) Remove the power connector (plug) from the main unit. (3) Loosen the three screws in the center of the Power Connector (plug). (4) Strip the sheath of the power cord, twist the wire ends, insert them into the bar terminals. (5) Fix them with screws. • Use a flat-blade screwdriver (size 0.6 x 3.5) to tighten the terminal screws. The torque required to tighten these screws is 0.
Chapter 4 Installation and Wiring 4.2.2 Connecting the Power Supply This section describes the precautions for supplying a power voltage. Twisted-pair cord Constant Voltage Transformer OT FG • If the supplied voltage exceeds the OT unit’s range, connect a constant voltage transformer. SEE Chapter 3 Specifications (page 3-1) Twisted-pair cord Insulating Transformer OT • For between the line and ground, select a power supply that is low in noise.
Magelis XBT OT User Manual 4.2.3 Grounding This section describes the precautions for grounding the OT unit. WARNING UNINTENDED EQUIPMENT OPERATION • Do not use common grounding, since it can lead to an accident or machine breakdown. Failure to follow these instructions can result in death, serious injury, or equipment damage. (a) Exclusive Grounding (BEST) • When supplying power to the OT unit, be sure to separate the OT Other Equipment input/output and power lines, as shown.
Chapter 4 Installation and Wiring 4.2.4 I/O Signal Line Placement • Input and output signal lines must be separated from the power control cables for operating circuits. • If this is not possible, use a shielded cable and connect the shield to the OT unit’s frame. 4.3 CF Card Insertion/Removal This section describes how to insert and remove a CF Card.
Magelis XBT OT User Manual 4.3.1 Inserting the CF Card Use the following steps to insert the CF Card in the OT. (1) Pull the CF Card Cover frontward and then open it upward. (2) Insert the CF Card in the CF Card Slot, until the eject button is pushed forward. Eject Button (3) Close the cover. (As shown.) • Make sure that the CF Card cover is closed when accessing the CF Card. 4.3.2 Removing the CF Card Simply reverse the steps shown in the previous “Inserting CF Card” explanation.
Chapter 4 Installation and Wiring 4.4 USB Cable Clamp Attachment/Removal This clamp is used to prevent the USB cable connected to the USB Host Interface on the bottom of the OT unit from being unplugged due to vibration or other causes. DANGER ELECTRIC SHOCK Unplug the unit’s Power Cord from the 24 VDC power supply prior to attaching or detaching any connector(s) to or from the unit. Failure to follow these instructions can result in death, serious injury, or equipment damage. 4.4.
Magelis XBT OT User Manual Removal To remove the clamp from the USB cables, push down on the clamp strap’s clip to release it while pulling up on the clamp. Clip Clamp 4.4.2 XBT OT4320 Series Attachment (1) Before starting the procedure, lift up the tab on both sides of the USB Holder and remove the USB Cover. Tab (2) Attach the USB holder to the USB Host Interface part of the main unit.
Chapter 4 Installation and Wiring (4) Attach the USB cover to fix the USB cable. Insert the USB cover into the tab of the USB holder. USB Holder Tab USB Cover • Check the up/down orientation of the USB cover to ensure that the USB cable is secured properly. Removal (1) Lift up the tab of the USB holder and then remove the USB cover as shown below. USB Holder Tab (2) 4.4.3 USB Cover After removing the USB cable, remove the picks pushing the USB holder from both top and bottom.
Magelis XBT OT User Manual (3) Insert the USB cable into the port. Fasten the band around the plug and secure it with the clamp. Clamp USB Cable USB Holder Removal To remove the clamp from the USB cables, push down on the clamp strap’s clip to release it while pulling up on the clamp.
5 Maintenance 1. Cleaning the Display 2. Periodic Check Points 3. Replacing the Installation Gasket 4. Replacing the Backlight This chapter explains steps and inspection criteria for proper maintenance of the operating terminal.
Magelis XBT OT User Manual 5.1 Cleaning the Display When the surface or frame of the display become dirty, soak a soft cloth in water with a neutral detergent, wring the cloth tightly, and wipe the display. CAUTION EQUIPMENT DAMAGE • Do not use hard or pointed objects to operate the touch-screen panel, since it can damage the panel surface. • Do not use paint thinner, organic solvents, or a strong acid compound to clean the unit.
Chapter 5 Maintenance 5.3 Replacing the Installation Gasket The installation gasket provides protection against dust and moisture. • A gasket which has been used for a long period of time may have scratches or dirt on it, and could have lost much of its water resistance. Be sure to change the gasket at least once a year, or when scratches or dirt become visible. • The OT unit installation gasket’s model number is as follows.
Magelis XBT OT User Manual • The gasket must be inserted correctly into the groove for the OT’s moisture resistance to be equivalent to IP65f. • Since the gasket is flexible but not elastic, be careful not to stretch it unnecessarily, as doing so could tear the gasket. • Be sure the gasket’s seam is not inserted into any of the unit’s corners, only in the straight sections of the groove. Inserting it into a corner may lead to its eventually tearing.