Data Sheet
Connections - terminals Control circuit : screw clamp terminals 2 ca-
ble(s) 1...2.5 mm² - cable stiffness: flexible - with ca-
ble end
Power circuit : screw clamp terminals 1 ca-
ble(s) 1.5...10 mm² - cable stiffness: solid - without-
cable end
Control circuit : screw clamp terminals 1 ca-
ble(s) 1...4 mm² - cable stiffness: flexible - without-
cable end
Control circuit : screw clamp terminals 2 ca-
ble(s) 1...4 mm² - cable stiffness: flexible - without-
cable end
Control circuit : screw clamp terminals 1 ca-
ble(s) 1...4 mm² - cable stiffness: flexible - with ca-
ble end
Control circuit : screw clamp terminals 1 ca-
ble(s) 1...4 mm² - cable stiffness: solid - without ca-
ble end
Control circuit : screw clamp terminals 2 ca-
ble(s) 1...4 mm² - cable stiffness: solid - without ca-
ble end
Power circuit : screw clamp terminals 1 ca-
ble(s) 2.5...10 mm² - cable stiffness: flexible - with-
out cable end
Power circuit : screw clamp terminals 2 ca-
ble(s) 2.5...10 mm² - cable stiffness: flexible - with-
out cable end
Power circuit : screw clamp terminals 1 ca-
ble(s) 1...10 mm² - cable stiffness: flexible - with ca-
ble end
Power circuit : screw clamp terminals 2 ca-
ble(s) 1.5...6 mm² - cable stiffness: flexible - with ca-
ble end
Power circuit : screw clamp terminals 2 ca-
ble(s) 2.5...10 mm² - cable stiffness: solid - without-
cable end
Tightening torque Control circuit : 1.7 N.m - on screw clamp terminal-
s - with screwdriver flat Ø 6 mm
Control circuit : 1.7 N.m - on screw clamp terminal-
s - with screwdriver Philips No 2
Power circuit : 2.5 N.m - on screw clamp terminal-
s - with screwdriver flat Ø 6 mm
Power circuit : 2.5 N.m - on screw clamp terminal-
s - with screwdriver Philips No 2
Operating time 4...19 ms opening
12...22 ms closing
Safety reliability level B10d = 1369863 cycles contactor with nominal load-
conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical-
load conforming to EN/ISO 13849-1
Mechanical durability 15 Mcycles
Operating rate 3600 cyc/h at <= 60 °C
Complementary
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc drop-out at 60 °C, AC 50/60 Hz
0.8...1.1 Uc operational at 60 °C, AC 50 Hz
0.85...1.1 Uc operational at 60 °C, AC 60 Hz
Inrush power in VA 70 VA at 20 °C (cos ϕ 0.75) 60 Hz
70 VA at 20 °C (cos ϕ 0.75) 50 Hz
Hold-in power consumption in VA 7.5 VA at 20 °C (cos ϕ 0.3) 60 Hz
7 VA at 20 °C (cos ϕ 0.3) 50 Hz
Heat dissipation 2...3 W at 50/60 Hz
Auxiliary contacts type Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Type mirror contact (1 NC) conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non-overlap time 1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact
Insulation resistance > 10 MOhm for signalling circuit
Contact compatibility M2
3