Connections
■ screw clamp terminals or connectors
Rated operational voltage 690 V
Rated operational current Ie max AC-3 (Ue ≤ 440 V) 9 A 12 A 18 A 25 A 32 A 38 A
Ie AC-1 (
θ ≤ 60° C) 25 A 32 A 40 A 50 A
Rated operational power 220/240 V 2.2 kW 3 kW 4 kW 5.5 kW 7.5 kW 9 kW
in category AC3 380/400 V 4 kW 5.5 kW 7.5 kW 11 kW 15 kW 18.5 kW
415/440 V 4 kW 5.5 kW 9 kW 11 kW 15 kW 18.5 kW
500 V 5.5 kW 7.5 kW 10 kW 15 kW 18.5 kW 18.5 kW
660/690 V 5.5 kW 7.5 kW 10 kW 15 kW 18.5 kW 18.5 kW
1000 V – – – – – –
Contactor type * LC1D09 LC1D12 LC1D18 LC1D25 LC1D32 LC1D38
Reversing contactor type * with mechanical interlock LC2D09 LC2D12 LC2D18 LC2D25 LC2D32 LC2D38
N spring terminals (1)
Add the figure 3 before the voltage code. Example: LC1D09P7 becomes LC1-093P7
N lug-clamps (2)
Add the figure 6 before the voltage code. Example: LC1D09P7 becomes LC1-096P7
N Faston connectors (3) 2 x 6.35 (power) and 1 x 6.35 (control) up to D12 only
Add the figure 9 before the voltage code. Example: LC1D09P7 becomes LC1-099P7
* Basic reference to be completed by adding the coil voltage code
Standard control circuit voltages
a supply
Volts 24 42 48 110 115 220 230 240 380 400 415 440 500
Contactors LC1D09…D150 (coils D115 and D150 with integral suppression device fitted as standard)
50/60 Hz B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7 S7
Contactors LC1D80…D115
50 Hz B5 D5 E5 F5 FE5 M5 P5 U5 Q5 V5 N5 R5 S5
60 Hz B6-E6F6-M6-U6Q6--R6-
c supply
Volts 12 24 36 48 60 72 110 125 220 250 440
Contactors LC1D09…D65A (coils with integral suppression device fitted as standard)
U 0.75…1.25 Uc JD BD CD ED ND SD FD GD MD UD RD
Contactors LC1D80…D95
U 0.85…1.1 Uc JD BD CD ED ND SD FD GD MD UD RD
U 0.75…1.2 Uc JW BW CW EW - SW FW - MW - -
Contactors LC1D115 and D150 (coils with integral suppression device fitted as standard)
U 0.75…1.2 Uc - BD - ED ND SD FD GD MD UD RD
Low consumption
Contactors LC1D09…D38 (coils with integral suppression device fitted as standard)
Volts c 5 12 20 24 48 110 120 250
U 0.7…1.25 Uc AL JL ZL BL EL FL ML UL
Example of complete reference: LC1D09P7
TeSys D
Contactors
0.06…75 kW