Datasheet

Hold-in power consumption in VA
7.5 VA at 20 °C (cos ϕ 0.3) 60 Hz
7 VA at 20 °C (cos ϕ 0.3) 50 Hz
Heat dissipation
2...3 W at 50/60 Hz
Auxiliary contacts type
Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Type mirror contact (1 NC) conforming to IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching current
5 mA for signalling circuit
Minimum switching voltage
17 V for signalling circuit
Non-overlap time
1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact
Insulation resistance
> 10 MOhm for signalling circuit
Environment
IP degree of protection
IP20 front face conforming to IEC 60529
protective treatment
TH conforming to IEC 60068-2-30
pollution degree
3
ambient air temperature for operation
-5...60 °C
ambient air temperature for storage
-60...80 °C
permissible ambient air temperature around the device
-40...70 °C at Uc
operating altitude
3000 m without derating
fire resistance
850 °C conforming to IEC 60695-2-1
flame retardance
V1 conforming to UL 94
mechanical robustness
Vibrations contactor open 2 Gn, 5...300 Hz
Vibrations contactor closed 4 Gn, 5...300 Hz
Shocks contactor open 10 Gn for 11 ms
Shocks contactor closed 15 Gn for 11 ms
height
85 mm
width
45 mm
depth
92 mm
product weight
0.365 kg
Offer Sustainability
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Compliant - since 0702 - Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Product environmental profile
Available
Product end of life instructions
Available
3 / 3