Standards
UL 508
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
Product certifications
BV
CCC
CSA
DNV
GL
GOST
LROS (Lloyds register of shipping)
RINA
UL
Connections - terminals
Control circuit : screw clamp terminals 2 cable(s)
1...2.5 mm² - cable stiffness: flexible - with cable
end
Power circuit : screw clamp terminals 1 cable(s)
1...4 mm² - cable stiffness: flexible - with cable end
Control circuit : screw clamp terminals 1 cable(s)
1...4 mm² - cable stiffness: flexible - without cable
end
Control circuit : screw clamp terminals 2 cable(s)
1...4 mm² - cable stiffness: flexible - without cable
end
Control circuit : screw clamp terminals 1 cable(s)
1...4 mm² - cable stiffness: flexible - with cable end
Control circuit : screw clamp terminals 1 cable(s)
1...4 mm² - cable stiffness: solid - without cable
end
Control circuit : screw clamp terminals 2 cable(s)
1...4 mm² - cable stiffness: solid - without cable
end
Power circuit : screw clamp terminals 1 cable(s)
1...4 mm² - cable stiffness: flexible - without cable
end
Power circuit : screw clamp terminals 2 cable(s)
1...4 mm² - cable stiffness: flexible - without cable
end
Power circuit : screw clamp terminals 2 cable(s)
1...2.5 mm² - cable stiffness: flexible - with cable
end
Power circuit : screw clamp terminals 1 cable(s)
1...4 mm² - cable stiffness: solid - without cable
end
Power circuit : screw clamp terminals 2 cable(s)
1...4 mm² - cable stiffness: solid - without cable
end
Tightening torque
Power circuit : 1.7 N.m - on screw clamp terminals
- with screwdriver flat Ø 6 mm
Power circuit : 1.7 N.m - on screw clamp terminals
- with screwdriver Philips No 2
Control circuit : 1.7 N.m - on screw clamp
terminals - with screwdriver flat Ø 6 mm
Control circuit : 1.7 N.m - on screw clamp
terminals - with screwdriver Philips No 2
Operating time
4...19 ms opening
12...22 ms closing
Safety reliability level
B10d = 1369863 cycles contactor with nominal
load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with
mechanical load conforming to EN/ISO 13849-1
Mechanical durability
15 Mcycles
Operating rate
3600 cyc/h at <= 60 °C
Complementary
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc drop-out at 60 °C, AC 50/60 Hz
0.8...1.1 Uc operational at 60 °C, AC 50 Hz
0.85...1.1 Uc operational at 60 °C, AC 60 Hz
Inrush power in VA
70 VA at 20 °C (cos ϕ 0.75) 60 Hz
70 VA at 20 °C (cos ϕ 0.75) 50 Hz
2 / 3