Data Sheet

Associated fuse rating 20 A gG at <= 690 V coordination type 2 for power-
circuit
25 A gG at <= 690 V coordination type 1 for power-
circuit
10 A gG for signalling circuit conforming-
to IEC 60947-5-1
Average impedance 2.5 mOhm at 50 Hz - Ith 25 A for power circuit
[Ui] rated insulation volt-
age
600 V for power circuit certifications CSA
600 V for power circuit certifications UL
690 V for power circuit conforming to IEC 60947-4-1
690 V for signalling circuit conforming-
to IEC 60947-1
600 V for signalling circuit certifications CSA
600 V for signalling circuit certifications UL
Electrical durability 0.6 Mcycles 25 A AC-1 at Ue <= 440 V
2 Mcycles 9 A AC-3 at Ue <= 440 V
Power dissipation per-
pole
0.2 W AC-3
1.56 W AC-1
Protective cover With
Mounting support Plate
Rail
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
Product certifications BV
CCC
CSA
DNV
GL
GOST
LROS (Lloyds register of shipping)
RINA
UL
Connections - terminals Control circuit : screw clamp terminals 2 ca-
ble(s) 1...2.5 mm² - cable stiffness: flexible - with ca-
ble end
Power circuit : screw clamp terminals 1 ca-
ble(s) 1...4 mm² - cable stiffness: flexible - with ca-
ble end
Control circuit : screw clamp terminals 1 ca-
ble(s) 1...4 mm² - cable stiffness: flexible - without-
cable end
Control circuit : screw clamp terminals 2 ca-
ble(s) 1...4 mm² - cable stiffness: flexible - without-
cable end
Control circuit : screw clamp terminals 1 ca-
ble(s) 1...4 mm² - cable stiffness: flexible - with ca-
ble end
Control circuit : screw clamp terminals 1 ca-
ble(s) 1...4 mm² - cable stiffness: solid - without ca-
ble end
Control circuit : screw clamp terminals 2 ca-
ble(s) 1...4 mm² - cable stiffness: solid - without ca-
ble end
Power circuit : screw clamp terminals 1 ca-
ble(s) 1...4 mm² - cable stiffness: flexible - without-
cable end
Power circuit : screw clamp terminals 2 ca-
ble(s) 1...4 mm² - cable stiffness: flexible - without-
cable end
Power circuit : screw clamp terminals 2 ca-
ble(s) 1...2.5 mm² - cable stiffness: flexible - with ca-
ble end
Power circuit : screw clamp terminals 1 ca-
ble(s) 1...4 mm² - cable stiffness: solid - without ca-
ble end
Power circuit : screw clamp terminals 2 ca-
ble(s) 1...4 mm² - cable stiffness: solid - without ca-
ble end
2