Datasheet
Product datasheet
Characteristics
LADC22
TeSys D -
auxiliary contact block
-
2 NO + 2 NC
-
screw-
clamps terminals
Main
Range of product
TeSys D
TeSys D control relay
TeSys F
Range
TeSys
Product or component type
Auxiliary contact block
Auxiliary contacts operation
Make before break
Pole contact composition
2 NO + 2 NC
Connections - terminals
Screw clamp terminals 1 cable 1...2.5 mm² - cable
stiffness: flexible - with cable end
Screw clamp terminals 1 cable 1...2.5 mm² - cable
stiffness: flexible - without cable end
Screw clamp terminals 1 cable 1...2.5 mm² - cable
stiffness: solid - with cable end
Screw clamp terminals 1 cable 1...2.5 mm² - cable
stiffness: solid - without cable end
Screw clamp terminals 2 cable 1...2.5 mm² - cable
stiffness: flexible - with cable end
Screw clamp terminals 2 cable 1...2.5 mm² - cable
stiffness: flexible - without cable end
Screw clamp terminals 2 cable 1...2.5 mm² - cable
stiffness: solid - with cable end
Screw clamp terminals 2 cable 1...2.5 mm² - cable
stiffness: solid - without cable end
Complementary
Mounting location
Front
[Ui] rated insulation voltage
690 V - conforming to IEC 60947-5-1
600 V - certifications CSA
600 V - certifications UL
[Ue] rated operational voltage
690 V AC 25...400 Hz
[Ith] conventional free air thermal current
10 A at <= 60 °C
Irms rated making capacity
140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
Permissible short-time rating
100 A at 60 °C 1 s
120 A at 60 °C 500 ms
140 A at 60 °C 100 ms
Protection type
GG fuse <= 10 A rating according to operational current for Ue <= 690 V
Associated fuse rating
10 A gG IEC 60947-5-1
Mechanical durability
3 Mcycles
Minimum switching current
5 mA
Minimum switching voltage
17 V
Non-overlap time
1.5 ms on de-energisation (no overlap between NC and NO contact)
1.5 ms on energisation (no overlap between NC and NO contact)
Overlap time
1.5 ms
Insulation resistance
> 10 MOhm
Product weight
0.05 kg
Environment
environmental characteristic
Normal environment
standards
BS 4794
EN 60947-5-1
IEC 60947-5-1
NF C 63-140
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.