User`s manual
170 BNO 681 00
82
Option for
remote bus
branch
Option for remote bus branch interface
Reconfiguration
input
Input voltage and current:
Relay output Mechanical and electrical data:
Relay output:
Voltage (output)
Voltage (output):
Relay output:
Switching cycle
Switching cycle:
Fiber optic adapter OPTOSUB or OPTOSUB PLUS (2 items maximum)
Signal level 1 signal +15 ... 30 VDC
Signal level 0 signal -30 ... +5 VDC
Input current 3 mA at 24 VDC
Construction of relay output
(not to be used for network
isolation)
potential free relay contact
The contacts of the relay output must be fitted with a
protective circuit when dealing with large loads, especially
inductive loads (RC combinations, varistor, or, with DC
voltages of an inverse diode).
Switching voltage for relay Max. 24 VDC
Switching current for contact min. 10 mA (only with new contacts)
Resistive load 2 A at 24 VDC
Lamp load 0.2 A at 24 VDC
Mechanical
1 x 10
8
, 3/s;
Electrical
1 x 10
5
, 20/min (2 A/30 VDC resistive load)
5 x 10
5
, 20/min (1 A/30 VDC resistive load)