User`s manual

170 BNO 671 00 / 170 BNO 671 01
68
Relay output Mechanical and electrical data:
Relay output:
Voltage (output)
Voltage (output):
Relay output:
Switching cycle
Switching cycle:
Construction of relay output
(not to be used for network
isolation)
potential free relay contact
The contacts of the relay output must be fitted with a
protective circuit when dealing with heavy loads, especially
inductive loads (RC combinations, varistor, or, with DC
voltages of a free-wheeling diode).
Operating voltage for relay 24 VDC
Switched current for contact min. 10 mA (only with new contacts)
Resistive load 0.5 A at 125 VAC
0.5 A at 110 VDC
2 A at 24 VDC
Lamp load 0.2 A at 24 VDC
Mechanical 1 x 108, 3/s;
Electrical 1 x 105, 20/min (2 A/30 VDC resistive load)
5 x 105, 20/min (1 A/30 VDC resistive load)