User`s guide

Bulletin No. VVDED397053US Section 3 — Controlling and Monitoring the ATV58 Drive Controller
November 2000 Hand/Off/Auto (HOA)
© 2000 Schneider Electric All Rights Reserved
29
CONTROL MODES
Hand/Off/Auto (HOA) Switch Functionality
When the control switch is in the auto position,
all local run and start
commands to the drive controller must be removed.
During power-up,
the ATV58 drive controller defaults to local control. (See “Local and
Remote Control” on page 30.) After the drive controller recovers from a
power up sequence (including such unplanned events as an AC line
power disturbance), it immediately responds to any local controls that are
active before the Interbus-S communication board has initialized and
assumed control.
This can result in unintended equipment operation.
When the control switch is in the hand or off position,
the drive controller
must be placed into the forced local mode .
While it is possible to stop
the drive controller in the remote mode by activating one of the local stop
commands (such as the keypad display stop button), commands sent
over the network can restart the drive controller if it is not in forced local
mode. See “Forced Local” on page 31.
LOSS OF CONTROL
The user must provide a Hand/Off/Auto switch with the following
functionality:
In the Hand position, forced local mode must be enabled.
In the Off position, all run terminal inputs must be disabled via
open circuit, and forced local mode must be enabled.
In the Auto position, the run terminal inputs must be disabled via
open circuit, and forced local mode must be disabled.
Failure to follow these instructions can result in death or serious
injury.
WARNING
VVDED397053USBook Page 29 Tuesday, November 28, 2000 9:01 AM