User`s guide

Section 3 — Controlling and Monitoring the ATV58 Drive Controller Bulletin No. VVDED397053US
Speed Function November 2000
28
© 2000 Schneider Electric All Rights Reserved
W604
or
16#6043
FRHD 1 rpm Speed Reference Value
Signed ramp output
Read only
W605
or
16#6044
RFRD 1 rpm Actual Speed
Motor Speed
Read only
W606
or
16#6046/1
SMIL 1 rpm Speed Min Max Amount
Low speed, equivalent to LSP (W251),
but in rpm
Read/Write
0 to HSP in rpm
W607 SMIH Reserved 0
W608
or
16#6046/2
SMAL 1 rpm Speed Min Max Amount
High speed, equivalent to HSP (W250),
but in rpm
Read/Write
LSP to TFR
W609 SMAH Reserved 0
W610
or
16#6048/1
SPAL 1 rpm Speed Acceleration
Speed for calculation of acceleration
ramp
Read/Write
1 to 65535
W611 SPAH Reserved 0
W612
or
16#6048/2
SPAT 1 s Speed Acceleration
Time for calculation of acceleration ramp:
Time required to go from 0 to SPAL
(W610)
Read/Write
0 to 65535
W613
or
16#6049/1
SPDL 1 rpm Speed Deceleration
Speed for calculation of deceleration
ramp
Read/Write
1 to 65535
W614 SPDH Reserved 0
W615
or
16#6049/2
SPDT 1 s Speed Deceleration
Time for calculation of deceleration ramp:
Time required to go from SPDL (W613) to
0
Read/Write
0 to 65535
Table 15: DRIVECOM Parameters (Continued)
Word Code Units Parameter Name and Description Possible Values or Range