User`s guide

Bulletin No. VVDED397053US Section 2 — Software Set-Up
November 2000 Interbus-S Protocol
© 2000 Schneider Electric All Rights Reserved
21
Get-OV
This is used to display how the parameters listed in Tables 8 and 9 on
pages 19 and 20 are setup.
Identify
This is used to identify the device, and is comprised of three types of data
as shown in Table 12.
Read/Write
This is used to read or write the value of a drive controller or Drivecom
object via its index and sub-index. The ATV58 Register Access Guide for
Communication Networks, VVDED397058US provides information for
making the connection between the index/sub-index and the drive
controller or Drivecom object details.
Table 11: Word 483 Display Register
Word Code Description Possible Values or Range
W483
or
0x5FE8/34
DF1
Register of active
faults no. 1 (no fault
if the bits = 0)
Bit 0 = 1: Incorrect calibration constants (INF)
Bit 1 = 1: Unknown drive controller rating (INF)
Bit 2 = 1: Unknown or incompatible option (INF)
Bit 3 = 1: HD (ASIC) initialization incorrect (INF)
Bit 4 = 1: EEPROM control board fault (EEF)
Bit 5 = 1: EEPROM power board fault (EEF)
Bit 6 = 1: Incorrect configuration (CFF)
Bit 7 = 1: Invalid configuration (CFI)
Bit 8 = 1: Normal communication link fault (SLF)
Bit 9 = 1: Fast communication link fault (ILF)
Bit 10 = 1: Fast communication “NET” fault (CNF)
Bit 11 = 1: External fault via normal serial link
(EPF)
Bit 12 = 1: External fault via fast serial link (EPF)
Bit 13 = 1: Motor short circuit fault (SCF)
Bit 14 = 1: Precharge relay closure too long
(CRF)
Bit 15 = 1: Precharge relay command cut-off
(CRF)
Table 12: Types of Identify Data
Name of Device Manufacturer Schneider Electric
Name of Model ATV58••••••
Device Version Number Example: V1.0
VVDED397053USBook Page 21 Tuesday, November 28, 2000 9:01 AM