User`s guide
Bulletin No. VVDED397053US Section 2 — Software Set-Up
November 2000 Set-Up with IBS PC Software
© 2000 Schneider Electric All Rights Reserved
15
SETUP WITH IBS PC SOFTWARE
To assist users familiar with Phoenix Contact IBS CMD G4 > V4.3
software (English version), this section describes the setup procedures
for the ALTIVAR 58 drive controller.
Device Description for ALTIVAR 58 Drive Controllers
Configuration of the Read Again Function
An ATV58 drive controller can be inserted into a project using the
automatic read function for the bus configuration: Read Again. This
function automatically recognizes the ATV58 as a drive controller which
conforms to the Drivecom Profile 21 (RemoteBus) with identification code
227.
To configure this function:
1. Right-click on the icon.
2. In the menu which appears, choose Description.
Table 6: Device Description
Device Number Automatic
Group Number —
Station Number —
Device Name ALTIVAR 58 Profile 21 (RB)
Manufacturer Name Schneider Electric
Device Type ALTIVAR 58
Order Number Undefined
Ident Code 227 (decimal)
Profile Number 21 (hex)
Process Data 32 bits
Parameter Channel 1 word
CR Automatic
Interface Type
Incoming Interface (IN1) Remote
Outgoing Interface (OUT1) Remote
Icon Drivecom 227
Parameter Channel
Message Lengths
Transmit: 128
Receive: 128
Supported Parameter
Channel Services
Read code: 80 30 00
Write
Get-OD (long format)
VVDED397053USBook Page 15 Tuesday, November 28, 2000 9:01 AM