Cable Routing Practices
When wiring the ATV58 drive controllers to an Interbus-S network, follow
all wiring practices required by national and local electrical codes.
When routing cable:
Avoid areas of high temperature, moisture, vibration, or other
mechanical stress.
Secure the cable where necessary to prevent its weight and the weight
of other cables from pulling or twisting the cable.
Use cable ducts, raceways, or other structures for protecting the cable.
These structures should be used for signal wiring paths and should not
contain power wiring.
Avoid sources of electrical interference that can induce noise into the
cable. Use the maximum practicable separation from such sources.
When planning cable routing within a building, follow these guidelines:
Maintain a minimum separation of 3.3 ft (1 m) from the following
equipment:
air conditioners and large blowers
elevators and escalators
radios and televisions
intercom and security systems
fluorescent, incandescent, and neon lighting fixtures.
Maintain a minimum separation of 10 ft (3 m) from the following
equipment:
power wiring
transformers
generators
—alternators
When wiring in electrical equipment rooms or large electrical equipment
line-ups, observe the following guidelines for cable segregation and
separation of circuits:
Use metallic conduit for drive controller wiring. Do not run control
network and power wiring in the same conduit.