Specifications

Fieldbus Communications Support
68
31004624 8/2009
Diagnostic Data
Introduction
This topic discusses the diagnostic and error data for the Advantys STB NIB 2212
INTERBUS NIM.
For a status word’s given selector value, the corresponding information is
transmitted in the word’s low byte.
NIM Status (Selector 00h)
When the selector value is 00, NIM status low byte information is transmitted as the
status word’s low byte value:
Bit Meaning of Value
D0 device failure
1 = any module on the island bus has failed
0 = no module failure
D1 internal failure
1 = any global diagnostic bit (except RESET) is set
0 = all global diagnostic bits are set to 0
D2 word length failure
1 = output or input data length exceeds its respective word limits
0 = output and input data lengths are within their respective word limits
D3 protected mode
1 = NIM in protected mode—RST button is disabled and the island configuration
requires a password to write to it
0 = NIM not in protected mode—RST button is enabled and the island configuration
is not password-protected
D4,
D5,
D6
error code
0x00 = no error
0x01 = self-test failed—ID code does not match first initialization, power reset
required
0x02 = at least one global bit has been set
0x03 = expired request timer
0x04 = empty assembly list
0x05 = expired confirm timer
0x06 = wrong island bus state at initialization
0x07 = an error code higher than 0x07 (reserved)