Specifications

The STB NIB 2212 NIM Module
30
31004624 8/2009
off blink: 2 off The NIM has detected a module assignment error; the
island bus is not started.
blink: 5 invalid internal triggering protocol
off blink: 6 off The NIM detects no I/O modules on the island bus.
blinking (steady) off The NIM detects no I/O modules on the island bus ... or ...
No further communications with the NIM are possible.
Probable causes:
z internal condition
z wrong module ID
z device did not auto-address (see page 44)
z mandatory module is incorrectly configured
(see page 96)
z process image is not valid
z device is incorrectly configured (see page 46)
z The NIM has detected an anomaly on the island bus.
z receive/transmit queue software overrun
on off off The island bus is operational.
on blink 3 off At least one standard module does not match. The island
bus is operational with a configuration mismatch.
on blink: 2 off There is a serious configuration mismatch (when a module
is pulled from a running island). The island bus is now in pre-
operational mode because of one or more mismatched
mandatory modules.
blink: 4 off off The island bus is stopped (when a module is pulled from a
running island). No further communications with the island
are possible.
off on off Internal condition: The NIM is inoperable.
[any] [any] on Test mode is enabled: The configuration software or an HMI
panel can set outputs. (See note 2.)
1 The TEST LED is on temporarily during the Flash overwrite process.
2 The TEST LED is on steadily while the device connected to the CFG port is in control.
RUN (green) ERR (red) TEST (yellow) Meaning