Specifications
1
2
3
4
5
6
7
8
9
10
81
Ethernet network
Cabling system
ConneXium
™
transceiver
Introduction
The use of ConneXium
™
transceivers makes it possible to perform the following:
b
Creation of linear ber optic bus topologies, for products with twisted pair cable
Ethernet connection
b Interfacing products with twisted pair cable Ethernet connection with a ber
optic cable
Transceivers are “plug and play” devices that do not need any conguration.
ConneXium transceivers provide ber optic wiring for transmission in areas
subject to interference (high levels of electromagnetic interference) and for long
distance communications.
Specications and reference
Transceivers
Interfaces Copper cable ports Number and type 1 x 100BASE-TX port
Shielded connectors RJ45
Medium Shielded twisted pair, category CAT 5E
Total length of pair 100 m
Fiber optic ports Number and type 1 x 100BASE-FX port
Connectors SC
Medium Multi-mode optical ber
Length of optical ber
50/125 µm ber 3000 m (1)
62.2/125 µm ber 3000 m (1)
Attenuation analysis
50/125 µm ber 8 dB
62.2/125 µm ber 11 dB
Redundancy P1 and P2 redundant power supplies
Power supply Voltage 24 V (18…32) c, safety extra low voltage (SELV)
Power consumption 160 mA (190 max. at 24 V c)
Removable connector 5-way
Operating temperature 0…+ 60 °C
Relative humidity 10…95% non condensing
Degree of protection IP 20
Dimensions W x H x D 47 x 135 x 111 mm
Mounting On symmetrical DIN rail, 35 mm wide
Weight 0.230 kg
Conformity to standards cUL 60950, UL 508 and CSA 22.2 No. 142, UL 1604 and CSA 22.2 No. 213 Class 1 Division 2,
e, GL, C-Tick
LED indicators P1 and P2 power supplies, Ethernet link/port status
Alarm relay Detected power supply fault, detected Ethernet network fault, or detected communication port
fault (1 A max. volt-free contact at 24 V c)
Reference 499 NTR 101 00
(1) Length dependent on the attenuation analysis and attenuation of the optical ber (typical
value: 2000 m).
DTEDTE
DTE
Linear topology on optical ber
Product data sheet