Specifications
1
2
3
4
5
6
7
8
9
10
67
Modicon
™
Momentum
™
automation platform
M1/M1E processor adapters
Environment
Type of processor 171 CCC 960 30 171 CCC 980 30
Temperature Operating °C 0...60
Storage °C - 40...85
Relative humidity 5...96% (non-condensing)
Altitude m 2000 (6,500 ft.)
Mechanical withstand
(immunity)
To vibrations 57...150 Hz @ 1 gn
10...57 Hz @ 0.075 mm d.a
To shocks
±
15 gn peak, 11 ms, half sine wave
Designed to meet UL, e, CUL, FM Class 1 Div. 2, NEMA 250 Type 1, and IP 20 conforming to IEC 529
Specications
Central processing unit (CPU) x 86 based IEC Executive
Word length bit 16
Material Lexan
Voltage Vdc 5.0 V (supplied by I/O Base)
Voltage tolerance
±
5% (as supplied by I/O Base)
RFI immunity/EMI susceptibility/Electrostatic discharge Meets e mark for open equipment.
Open equipment should be installed in an industry standard enclosure, with access
restricted to qualied service personnel
Di-electric strength Comm port is non-isolated from logic common
Indicator lights Processor adapter operating (RUN), Ethernet network status (LAN Act) and Ethernet
network activity (LAN STS)
Power source Power supply on-board the Modicon
™
Momentum
™
I/O Base
Flash memory Mb 1
Clock speed MHz 50
Scan time ms/K 3
Communication ports 1 Ethernet
2 I/O Bus (derivative of I
n t e r Bus) Dedicated RS 485 Modbus
Capacity 984 LL program memory K 18
IEC program memory K 200
Data memory K 24
Discrete I/O 8192 In/8192 Out (A total of 8192 bits can be congured for discrete and analog I/O,
any mix up to the stated limits)
Register I/O 26048 In/26048 Out (A total of 26048 words can be congured for discrete and analog
I/O, any mix up to the stated limits)
I/O limit 8192 bits max. :
- 4096 In/4096 Out on I/O Bus
- I/O can be extented using a
Modbus Plus
™
option adapter and
Peer Cop (2048 In/Out)
- I/O local on Modbus
™
- I/O can be extented using a Modbus Plus
option adapter and Peer Cop
(2048 In/Out)
Transparent Ready services Class B10
Web services “Rack Viewer” access to the product description and status, and to the island
diagnostics
“Data editor” access to the conguration functions and variables
“Web page loader” software tool for loading user Web pages
Ethernet TCP/IP communication
management services
Modbus Messaging (read/write data words)
I/O Scanning
I/O bus addressing 80 I/O drops with ProWORX
™
,
128 I/O drops with Concept
™
–
References:
page 68
Specications (continued)