Introduction
The FIPIO™ communication adapter can be plugged into a Modicon™ Momentum™
I/O base to create a functional I/O unit on the FIPIO bus, and to provide a direct
connection to the FIPIO Network for the full family of Modicon Momentum I/O modules.
This connectivity enables the Modicon Momentum I/O to be used along with other
FIPIO compatible control devices, including: industrial computers, operator control
stations, drive systems, and other controls to provide a exible, time-critical,
cost-effective solution for distributing I/O modules throughout a large area.
There are two types of communication adapters available:
170 FNT 110 01
(1) for a FIPIO bus connected to a Modicon
Premium
PLC
170 FNT 110 00 for a FIPIO bus connected to TSX 7 series CPUs or APRIL 5030
and 5130 CPUs
Each Modicon Momentum I/O module is an individual node or device on the FIPIO
network with its address set by the user on the dual rotary switch on the front of the
communication adapter. FIPIO is a network that can have up to 128 slave devices.
The FIPIO network’s distance and communication capabilities range from 1000 meters
(3330 ft.) to 15000 meters (45000 ft) with repeaters over twisted pair cable at a data
rate of 1 Mbit/s.
(1) The FIPIO communication adapter 170 FNT 110 01 does not support the 170 ADM 540 80
I/O base.
Description
The 170 FNT 110 0p communication module features the following:
1 Three indicator lights (LEDs):
Ready indicator light (green): module powered up or in service-
COM indicator light (yellow): data being sent or received-
ERR indicator light (red): inoperative device-
2 9-way male SUB-D connector for connecting to FIPIO bus
3 Slot for identication label (supplied with I/O sub-bases)
4 Two switches for coding slave address on the bus