Installation manual
InRow RC Installation Manual32
Electrical Connections
The following electrical connections are required in the field:
• Controls (user interface, Network Management Card)
• Communication (A-Link, Building Management System)
• Power
NOTE: All electrical connections must be in accordance with local and national codes and regulations.
See the equipment nameplate for voltage and current requirements.
All low-voltage connections, including data and control connections, must be made with properly insulated
wires. Low-voltage wiring must be insulated based on the wiring with which it is routed. Wiring does not require
300-V insulation if it is separated from line voltage wiring. However, it will need 600-V insulation if it is wired in
the same cable tray as 480-VAC wiring.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Potentially dangerous and lethal voltages exist within this unit. More than one disconnect
switch may be required to energize or de-energize this equipment. Observe all cautions
and warnings. Failure to do so could result in serious injury or death. Only qualified
service and maintenance personnel may work on this equipment.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work
practices. See NFPA 70E or CSA Z462.
• This equipment must be installed and serviced by qualified personnel only.
• Turn off all power supplying this equipment before working on or inside the equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors, and covers before turning on power to this equipment.
Failure to follow these instructions will result in death or serious injury.










