Installation manual

27InRow RC Installation Manual
5. Position the insulated chilled water
supply pipe
in the equipment.
Mount the gasket
and connect the
pipe to the union. Tighten the union to
20 Nm (14.8 ft-lb).
6. Insulate the joint with the provided
insulation (not shown).
7. Reinstall the air filter bracket
.
8. Reinstall the rear condensate drain
pan bracket
and the air filters.
9. Connect the water supply pipe
to
the field-installed water supply
using the gasket
saved from step
5, union end
, and union nut
.
na2576a