Installation manual

17InRow RC Installation Manual
Service access
An area of minimum 900 mm (36 in.) of clear floor space in front of and behind the equipment is recommended
for servicing (208V equipment), or 1067 mm (42 in.) for servicing 400V and 480V equipment. All required
normal maintenance can be performed from the front or rear of the equipment while in the row.
An area of minimum 1200 mm (48 in.) of clear floor space in front of or behind the equipment is recommended
to roll the equipment out of a row.
NOTE: Check local and national codes and regulations for further service access requirements.
Dimensions are shown in mm (in.).
1200 (48.00)
1200
(
48.00)
na1825a
900 (36.00)
900 (36.00)
MAINTENANCE
ACCESS
REQUIRED
WHEN
LOCATED IN
THE ROW
ACCESS
REQUIRED TO
ROLL OUT OF
THE ROW