Planning Instruction 66571758GB0 49/2011 Fire Detection FX 3NET + SLC FIRE ALARM SYSTEM Part 1: General Rules These are the planning instructions for an FX 3NET fire detection and alarm system consisting of FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET control panels SLC compatible intelligent field devices In this document FX refers to all FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET panels. For information specifically related to a specific panel model, that model type is indicated.
Planning Instruction 66571758GB0 Fire Detection 2 Contents About planning the system ............................................................................................................................... 3 1.1 When is a fire alarm needed? ................................................................................................................... 3 1.2 Planning an automatic fire alarm system................................................................................................
Planning Instruction 66571758GB0 1. About planning the system 1.1 When is a fire alarm needed? Fire Detection 3 Fire detection and alarm systems are installed mainly to protect human life. The early detection of smoke sensor alerts people to evacuate the building in an orderly manner. Alarm devices provide a sufficient signal to warn people. Fire detection and alarm systems are also installed on premises where stock, machinery or other property need to be protected.
Planning Instruction 66571758GB0 1.3 Fire Detection 4 Regulations EN54-14 “Guidelines for Planning, Installation, Commissioning and Maintenance” defines good general guidelines for planning. Local specific regulations must also be followed. The main planning and documentation phases are described in the diagram below. A typical lay out drawing including devices is found in the section 1.4.
Planning Instruction 66571758GB0 1.4 Fire Detection 5 Example of a site plan for the FX 3NET fire detection system 001 002 01.014 003 004 01.015 005 01.016 01.017 006 01.018 007 01.019 01.020 01.024 01.013 01.012 XE 01.021 01.022 01.023 016 008 To FCP-1 24 VDC (From FCP-1) CTLE CTLE 01.011 011 01.001 01.002 01.003 01.010 01.005 012 01.004 009 010 01.161 To FIRE DOOR 01.006 RE 015 01.101 013 CZ CONTROL PANEL 01.151 FCP-1 C CTLE 60° 01.
Planning Instruction 66571758GB0 Fire Detection 2. General description of the FX 3NET system 2.1 Standalone FX 3NET or FXL 3NET fire detection system Main features The modular design of the FX 3NET and FXL 3NET 2, 4, 6, or 8 loop control panel offers a competitive solution for small and medium sized projects. The address capacity of the detection circuits also offers flexibility for cabling, thus saving costs in installation work.
Planning Instruction 66571758GB0 2.3 Fire Detection FXS 3NET fire detection panel Main features The FXS control panel offers the same features as the FX and FXL and FXM panels, but in a smaller format and without any built-in power supply unit. In the FXS panel, there is one card slot for an option board. FXS 3NET standalone panel metrics 1 ...
Planning Instruction 66571758GB0 2.
Planning Instruction 66571758GB0 2.6 Fire Detection 9 Networked FX 3NET system diagram FX_ 1 2 FMPX FX_ 1 4 5 3 6 7 2 1 0 9 8 4 3 2 10 5 9 4 3 2 10 6 7 8 x10 5 9 6 7 8 4 5 3 6 7 2 8 10 9 x10 C 2 C FXM 1 2 FX_ REPX MCOX FXS Note! When the INFO serial communication is used, the maximum address capacity per detection circuit is 214: lower address range 1...159 + higher address range 201...255.
Planning Instruction 66571758GB0 3. Fire Detection 10 FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET construction The FX panel is a modular construction, facilitating easy expansion and selection of required modules. The panel consists of a back plate in sheet metal, specially designed racks that hold the electronic boards and a cover in plastic.
Planning Instruction 66571758GB0 FXL 3NET cabinet The FXL cabinet has space for the following - 1 x UI2 - 1 x MC2 - 1 x PS (4,0A) - Option board (OP) totally 9 pcs: SLC, max. 4 pcs CLC, max. 4 pcs IOC, max. 4 pcs OCA, max. 4 pcs MCOX-OB, max. 1 pcs REPX-OB, max. 1 pcs ZLPX-IC, max. 1 pcs 3.3 OP OP OP PS OP MC2 OP B B FXS 3NET cabinet The FXS cabinet has space for the following - 1 x UI2 - 1 x MC - Option board (OP) totally 1 pcs: SLC, max. 1 pcs CLC, max. 1 pcs IOC, max. 1 pcs OCA, max.
Planning Instruction 66571758GB0 3.5 Fire Detection 12 FX battery cabinet The FX battery cabinet has space for the following - 4 x battery 12V / 17Ah - Fire alarm and Fault warning router B = Battery 3.6 B B B B FXM battery cabinet The FXM battery cabinet has space for the following 4 x battery 12V / 12Ah B = Battery B B © 2009 Schneider Electric. All rights reserved.
Planning Instruction 66571758GB0 Fire Detection 4. Mechanical installation 4.1 Installation, FX 3NET and FXL 3NET control panels 13 The mounting surface must be flat and it must bear the weight of the control panel and the chart file cabinet. The weight of the control panel excl. batteries is 11 kg and incl. batteries (2 x 17 Ah) 23 kg. The weight of the chart file cabinet is 9 kg. The mounting must be made directly on the wall surface, without any distance bushings or similar, to ensure IP30 rating.
Planning Instruction 66571758GB0 4.2 Fire Detection 14 Installation, FXM 3NET control panel The mounting surface must be flat and it must bear the weight of the control panel and the chart file cabinet. The weight of the control panel exl. batteries is 8 kg and incl. batteries 20 kg. 42 The weight of the battery cabinet is exl. batteries is 4 kg and incl. batteries 28 kg. 160 The weight of the chart file cabinet is 9 kg.
Planning Instruction 66571758GB0 4.3 Fire Detection 15 Installation, FXS 3NET control panel The mounting surface must be flat and it must bear the weight of the control panel and the chart file cabinet. The weight of the control panel is 4.4 kg. The weight of the chart file cabinet is 9 kg. 328 160 40 The mounting must be made directly on the wall surface, without any distance bushings or similar, to ensure IP30 rating. 32 FXS control panel © 2009 Schneider Electric. All rights reserved.
Planning Instruction 66571758GB0 5. Fire Detection 16 FX 3NET, multi-panel networked system FX 3NET is the solution for fire detection systems that consists of several individual panels and which interact with each other as if they were one huge panel. Any panel (or all of them) can handle the whole system.
Planning Instruction 66571758GB0 Fire Detection 17 Example 2 Consider an industrial site with two large buildings and a gate building. The gate should see all events to be able to direct the fire brigade. Each building should have (as in the previous example) mutual monitoring and control between the panels in the building, but there is no need to see the alarms between the buildings.
Planning Instruction 66571758GB0 5.2 Fire Detection 18 Site plan table of seeing – visible panels Site: Seeing panel Location Visible panels Number of connections 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Total number of connections Max. 256 The logical connection between the panels is based on configured "seeing" - "visible" relationships.
Planning Instruction 66571758GB0 5.3 Fire Detection 19 Interpanel communication In large systems with several panels, and especially if the panels are located apart, it is important to ensure the communication between the panels. Therefore the FX 3NET communication is secured with two separate communication lines (System 1 and System 2). If one line is broken or shorted, the system is still able to communicate with the other one. This redundancy also includes the communication circuitry in the panels.
Planning Instruction 66571758GB0 Fire Detection 6. Addressable detection circuits, addresses, zones 6.1 FX-SLC addressable detection circuits and addresses 20 The cables that connect the detectors and the I/O-modules to the panel are called detection circuits (or loops).
Planning Instruction 66571758GB0 6.2 Fire Detection 21 Detection zones Detectors in a fire detection system are usually grouped into ‘detection zones’. In conventional systems, the detection circuit coincides with a detection zone, but in addressable systems such as the FX 3NET, the detectors are grouped by the software. The zones are identified by a four-digit number in the range 0001 … 9999 and they have to be consecutive within an FX panel.
Planning Instruction 66571758GB0 Fire Detection 22 Closed detection circuit (highly recommended) A closed detection circuit gives the highest safety because the panel can still communicate with all addresses even if the cable is cut. To minimise the effect of a short circuit, isolators are available, which reduces the number of dropped-out addresses to the addresses between the isolators that are closest to the short circuit. The rule of a max.
Planning Instruction 66571758GB0 6.4 Fire Detection 23 FX control groups Note! See the document “Configuration data”. Note! See the user manual of the WinFX3Net configuration tool. The concept of control groups in an FX panel is a way of grouping the various inputs of the panel to facilitate the activation of outputs. The control groups are defined separately from the detection zones. ‘Control groups’ goes hand in hand with ‘events’. There are two kinds of events: input events and output events.
Planning Instruction 66571758GB0 Fire Detection 24 6.4.1 Control groups for all event types (Ctrl A and Ctrl B) Control group A and B inputs are not limited to the detectors and other addressable devices in the loop; monitoring inputs in the panel can also be members of control groups. Control group outputs can also be both addressable outputs in the loop as well as relay outputs in the panel.
Planning Instruction 66571758GB0 Fire Detection 25 Sequence example 2: reset during delay Fire Silence Reset (short press) 10s 12s Re-sound Input (e.g. MCP in alarm state) Fire alarm device Fire alarm device (10s delay) Fire Output Fire Output (10s delay) Fire Output (12s delay) Note! “Silence” affects only the fire alarm device outputs. Note! The shortest delay is always displayed on the user interface display if more than 1 delay is activated. 6.4.
Planning Instruction 66571758GB0 Fire Detection 26 6.4.4 Control group use for delayed alarm Control groups A and B can be used together with the DAPX alarm panel for a delayed alarm according to the Swedish standard. The “delayed alarm” functional principle has been described in the following diagram.
Planning Instruction 66571758GB0 6.5 Fire Detection 27 Number of devices between short circuit isolators Using short circuit isolators and returning the detection circuit to the panel, the full capacity of the detection circuit can be used. Short circuit isolators have to be installed at the boundary of each zone to comply with the requirement that not more than one zone falls out of operation in the case of a single cable fault. Note! 6.6 Use the system capacity calculation tool.
Planning Instruction 66571758GB0 7. FX-CLC Conventional detection circuits 7.1 Conventional detection circuit controller (CLC) Fire Detection 28 The FX 3NET panels can also be equipped with Conventional Loop Controllers (CLC). The CLC board takes one loop controller place in the panel.
Planning Instruction 66571758GB0 EOL resistor, Exi Max cable resistance Max detector load 8V 5V 3V 1V 0V 7.
Planning Instruction 66571758GB0 8. Cabling 8.
Planning Instruction 66571758GB0 8.2 Fire Detection 31 Cables of conventional detection circuits CLC, alarm device lines, input/output lines 8 9 10 11 FX_ No 8 9 10 Conventional detection circuits of a CLC board FX alarm device lines - fire bell, siren line - fault buzzer line FX clean contact input lines FX clean contact output lines Conductors x area 2 x 0.5 mm2 + shield 2 x 1.0 mm2 + shield Max. length Comments 1200 m (100 ) 2400 m (100 ) The cable resistance of the loop is max.
Planning Instruction 66571758GB0 8.3 Fire Detection 32 Cables of serial communication lines and power supply DAPX 13 FX_ 15 18 16 12 MCOX 13 FX_ 18 16 13 REPX 18 13 FMPX 18 12 14 17 FXS 12 12 17 13 18 Cable connection Serial connection - other FX panels - System 1 and System 2 Serial connections and power supply to FXS - System 1 and System 2 (RS285) - Operating voltage 2 pcs (21…30 VDC) Serial connections and power supply - INFO (RS485) Conductors x area Max.
Planning Instruction 66571758GB0 8.4 Fire Detection Grounding of communication cables TR+ TRTR+ GND 2a 2b, Spare wire, not in use 2b, Spare wire, not in use 1a 1a 1b 2a FX x chassis FX y chassis FMPX 2a 1a © 2009 Schneider Electric. All rights reserved. 1b 1a TR+ 1b RS485 GND 2b, Spare wire, not in use TR- TR- Cable shield is connected ONLY in FXNET panel All serial communication cable shields are connected to the grounding filter.
Planning Instruction 66571758GB0 8.5 Fire Detection 34 Battery backup calculation The formula for calculating the required battery capacity is: (L1 x T1 + L2 x T2) x 1.25 [Ah] where L1 = standby current in amperes T1 = standby time in hours L2 = alarm current in amperes T2 = alarm time in hours 1.25 = compensation for ageing The requirements for standby time and alarm time varies in various countries, but if no national requirements exist, it is recommended to use T1 = 72 hours and T2 = 0.5 hours.
Planning Instruction 66571758GB0 Fire Detection 9. FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET Technical data 9.1 Technical data, standard panels Dimensions (h*w*d) [mm] Weight (fully equipped, excl.
Planning Instruction 66571759GB0 49/2012 Fire Detection FX 3NET + SLC FIRE ALARM SYSTEM Part 2: System Devices These are the planning instructions for an FX 3NET fire detection and alarm system consisting of FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET control panels SLC compatible intelligent field devices In this document FX refers to all FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET panels. For information specifically related to a specific panel model, that model type is indicated.
Planning Instruction 66571759GB0 Fire Detection 2 Contents System devices .................................................................................................................................................. 3 Control equipment ..................................................................................................................................... 3 1.1 Intelligent/addressable AP200 series devices ...................................................................................
Planning Instruction 66571759GB0 1. Fire Detection 3 System devices Note! Technical information for the devices can be found in the data sheets. 1.1 Control equipment Basic panels FX 3NET FXL 3NET Control panels FXM 3NET FXS 3NET Basic control panel without detection circuits. Expandable to max. 8 detection circuits in steps of 2. Number of card slots for option boards is 5. Basic control panel without detection circuits. Expandable to max. 8 detection circuits in steps of 2.
Planning Instruction 66571759GB0 Fire Detection 4 Cabinet and frames FX-CAB FXM-CAB FX-MAP Cabinets and frames AX/FX/IX-BAT FXM-BAT FX-RMFW FXM-RMFW Mounting cabinet. FX control panel sized box for mounting of extra relays, modules, etc. Mounting cabinet. FXM control panel sized box for mounting of extra relays, modules, etc. Mounting cabinet. FX control panel sized box for orientation charts and other documentation. Also space for alarm router equipment. Battery cabinet.
Planning Instruction 66571759GB0 1.
Planning Instruction 66571759GB0 Fire Detection 6 Addressable I/O modules EM210E-CZ Conventional zone modules EM210E-CZR Monitor modules EM210E EM220E EM201E EM201E-240 Control modules EM201E-240-DIN B524RTE-W Combined monitor and control module Special detectors Duct detector housing EM221E DNRE Address module for standard conventional detectors and manual call points as well as for beam detectors, flame detectors and other special detectors. EOL-unit = 50µF. Cannot be used with Exi barriers.
Planning Instruction 66571759GB0 1.3 Fire Detection 7 Intelligent/addressable 200 series devices Note! The following devices can be used in the FX-SLC detection circuit but the maximum number of these devices per loop is 20. The maximum detection circuit cable resistance is 40 Ω. Intelligent high sensitive smoke detectors LZR-1M Laser smoke detectors 7251 Intelligent detectors for special applications EB6500 Beam detector EB6500S 1.
Planning Instruction 66571759GB0 Fire Detection 8 Alarm devices, beacons and alarm indication panels MBF-6EV Bell for indoor use MBA-6+BBX4 Bell for outdoor use, IP57 EMA1224B4R Sounder, for wall mounting EMA1224FR DBS1224B4W Sounder, for mounting beneath the detector base Alarm devices, DBS1224FW Beacons EMA24FRSSR Sounder/beacon EMA24RS2R Beacon, for indoor use XB-713111/1W Beacon, IP65, 1W XB-713311/3W Beacon, IP65, 3W Alarm indication panels LEDFF01 Indicators for fire alarm and fault warning Remote
Planning Instruction 66571760GB0 49/2011 Fire Detection FX 3NET + SLC FIRE ALARM SYSTEM Part 3: Additional Information These are the planning instructions for an FX 3NET fire detection and alarm system consisting of FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET control panels SLC compatible intelligent field devices In this document FX refers to all FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET panels. For information specifically related to a specific panel model, that model type is indicated.
Planning Instruction 66571760GB0 Fire Detection 2 Contents Examples of FX 3NET system structure .......................................................................................................... 3 System structure examples ...................................................................................................................... 3 1.1 Cable length of a segment ........................................................................................................................ 6 1.
Planning Instruction 66571760GB0 1. Examples of FX 3NET system structure 1.
Planning Instruction 66571760GB0 Fire Detection 4 Example 3: FX 3NET communication segments, long distances S1 Segment 0 Max. 1000 m S2 FX_ C C M M FX_ Max. 5 km *) FX_ Root Segment 1 FX_ M M C C FX_ S1 Max. 1000 m S2 C C C C M M M M M M C C FX_ FX_ S1 Segment 2 Max. 1000 m S2 FX_ Modem Link Max. 5 km *) FX_ FX_ M M C C FX_ S1 Segment n Max.
Planning Instruction 66571760GB0 Fire Detection 5 Example 4: Factory area FX_ S1 Segment 3 FX_ S2 ML S1 ML Segme nt 2 S2 FX_ FR E FX_ S1 ML S2 ML F X_ Segment 4 S1 ML ML Segment 1 S2 ML ML ML ML F X_ FX _ Segment 5 S1 FX_ S1 Segment 6 S2 S2 ML = Modem Link (max.
Planning Instruction 66571760GB0 1.2 Fire Detection 6 Cable length of a segment Max. 1000 m FX_ FX_ FX_ FX_ a FX_ c b FX_ FX_ © 2009 Schneider Electric. All rights reserved. a + b+ c = maks. 1000 m Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Document Number 66571760GB0 Telephone: +358 10 446 511 Fax: +358 10 446 5103 49 2011 www.pelco.
Planning Instruction 66571760GB0 2. Fire Detection 7 Control group examples Examples Fire alarm Fire alarm outp. 'Local' 17 17 17 21 Fire alarm Fire alarm Fire alarm Fire alarm outp. Fire alarm outp. Fire alarm outp. 'General' 'Local' 003; 021 17 21 Fire alarm Fire alarm outp. 003; 17 21 Fault alarm Fire alarm outp.
Planning Instruction 66571760GB0 3. Fire Detection 8 Special features to avoid nuisance alarms It is a well-known fact that fire detection and alarm systems, while operating fully according to standards and specifications, may initiate alarms in situations that are not really fire situations. These alarms are called nuisance alarms and are mostly the result of activities in the building that create physical phenomena that resemble those that the fire detection system is designed to react upon.
Planning Instruction 66571760GB0 Fire Detection 9 The initial delay time and the additional delay time are set in 10-second increments and are limited by the standard to a maximum of 5 minutes and 10 minutes, the total delay time being further restricted to a maximum of 10 minutes. Delayed alarm mode is selected individually for each address (normally only for smoke detectors). Delay is terminated by a non-delayed alarm signal (normally heat detector or manual call point).
Planning Instruction 66571760GB0 Fire Detection 4. FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET connections, settings and fuses 4.
Planning Instruction 66571760GB0 4.
Planning Instruction 66571760GB0 4.
Planning Instruction 66571760GB0 4.
Planning Instruction 66571760GB0 4.5 Fire Detection Connectors on the PS board Terminal name Connector symbol Purpose Description 30 VAC BATT PO 1 PO 2 4.
Planning Instruction 66571760GB0 4.7 Fire Detection 15 Connectors on each CLC board Terminal name Connector symbol Purpose 1 + Conventional line 1 Conventional line 1 + + Conventional line 16 - Description … 16 Conventional line 16 + + 16 - + 15 - + 14 - 4.
Planning Instruction 66571760GB0 4.
Planning Instruction 66571760GB0 Fire Detection 17 4.10 FX 3NET, FXL 3NET and FXM 3NET Fuses The 30VAC input from the transformer is protected with a T6.3A (FX 3NET and FXL 3NET) or T3.15A (FXM 3NET) fuse. The fuse is located on the FX-PS board. The battery connection is protected with a T6.3A fuse. The fuse is located on the FX-PS board. All other outputs are electronically protected against over-current and do not therefore have fuses. PO 2 PO 1 BATT +24V- +24V- + © 2009 Schneider Electric.
Planning Instruction 66571760GB0 Fire Detection 18 4.11 FX 3NET, FXL 3NET and FXM 3NET Battery backup The FXM cabinet has space for 2 x 12 Ah / 12 V batteries (in series connection for 12 Ah / 24 V). The FX cabinet has space for 2 x 17 Ah / 12 V batteries (in series connection for 17 Ah / 24 V). The FXL cabinet requires a separate battery cabinet (FX-BAT), which provides space for 2 x 2 x 17 Ah / 12 V batteries (parallel connection of two in series connected pairs of batteries for 34 Ah / 24 V).
Planning Instruction 66571760GB0 5. FX Settings and configuration 5.1 Settings in the FX panel Fire Detection 19 Settings on the FX-MC2 board With settings on the FX-MC2 board, the following can be set and selected: The identification number of the panel in a multipanel system. Whether the alarm device lines, controlled by the MC should be pulsed or continuously sounding.
Planning Instruction 66571760GB0 Fire Detection 20 Settings on the FX-CLC board With settings on the FX-CLC board, the following can be set and selected: The identification number of the CLC. ID number jumper settings ID 1. 2. + 16 - + 15 - 3. + 14 - 4. + 13 - Settings on the FX-OCA board With settings on the FX-OCA board, the following can be set and selected: The identification number of the OCA. ID number jumper settings ID CO16 CO14 CO12 1. 2. J1 J2 3.
Planning Instruction 66571760GB0 Fire Detection 21 Settings on the FX-IOC board With settings on the FX-IOC board, the following can be set and selected: - The identification number of the IOC. - Whether the alarm device lines, controlled by the IOC should be pulsed or continuously sounding. ID number jumper settings ID 1. 2. 3. IN 4 + IN 3 - + IN 2 - + IN 1 - + CO 2 CO 1 - PO 2 +24V- © 2009 Schneider Electric. All rights reserved. 4.