Installation Instruction 66571764GB3 16/2012 FX 3NET FIRE ALARM SYSTEM Installation and commissioning manual Read this manual carefully before installation and commissioning! Installation and commissioning must be performed according to this manual. This Installation and Commissioning Manual is to be kept together with the control panel.
Installation Instruction 66571764GB3 Fire Detection 2 Contents About this document ...........................................................................................................................................4 Typical placement of the units in a panel .........................................................................................................4 Installation, FX and FXL - control panels ..............................................................................................
Installation Instruction 66571764GB3 3 FX and FXL panel external connections, ALC ...................................................................................... 46 FXM panel external connections, SLC .................................................................................................. 47 FXM panel external connections, ALC .................................................................................................. 48 FXS panel external connections, SLC ..........................
Installation Instruction 66571764GB3 1. Fire Detection 4 About this document For non-experienced installers this document provides sufficient information to install the FX_ panel (FX, FXL; FXM, FXS) and to commission the whole system successfully. Experienced installers may select to connect all loops and IO connections at once without testing the connections in between.
Installation Instruction 66571764GB3 Fire Detection 5 FXL cabinet The FXL cabinet has space for the following - 1 x UI2 - 1 x MC2 - 1 x PSB (4.0 A) - Option board (OP) total 9 pcs: SLC/ALC/CLC, max. 4 pcs IOC, max. 4 pcs OCA, max. 4 pcs MCOX-OB, max. 1 pcs REPX-OB, max. 1 pcs ZLPX-IC, max. 1 pcs MC2 OP OP OP PSB OP FXM cabinet The FX battery cabinet has space for the following - 1 x UI2 - 1 x MC2 - 1 x PSA (2.2 A) - 2 x Battery (B) 12 V / 12 Ah - Option board (OP) total 2 pcs: SLC/ALC/CLC, max.
Installation Instruction 66571764GB3 Fire Detection 6 AX/FX/IX-BAT battery cabinet The FX battery cabinet has space for the following - 4 x battery 12 V / 17 Ah - Fire alarm and Fault warning router B B B B FXM-BAT battery cabinet The FXM battery cabinet has space for the following - 4 x battery 12 V / 12 Ah B B © 2009 Schneider Electric. All rights reserved.
Installation Instruction 66571764GB3 Fire Detection 7 FX-CAB mounting cabinet © 2009 Schneider Electric. All rights reserved. FXM-CAB mounting cabinet Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Document Number 66571764GB3 Telephone: +358 10 446 511 Fax: +358 10 446 5103 16 2012 www.pelco.
Installation Instruction 66571764GB3 Fire Detection 8 FXM-RMFW mounting frame FXM/ FXM-RMFW FXM + FX-MAP/ FXM-RMFW + FX-RMFW FXM + FXM-BAT +FX-MAP/ 2 x FXM-RMFW + FX-RMFW © 2009 Schneider Electric. All rights reserved. FXM-RMFW Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Document Number 66571764GB3 Telephone: +358 10 446 511 Fax: +358 10 446 5103 16 2012 www.pelco.
Installation Instruction 66571764GB3 Fire Detection 9 FX-RMFW mounting frame FX/ FX-RMFW FX + FX-MAP/ 2 x FX-RMFW FX + FX-MAP +FX-BAT/ 3 x FX-RMFW © 2009 Schneider Electric. All rights reserved. FX-RMFW Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Document Number 66571764GB3 Telephone: +358 10 446 511 Fax: +358 10 446 5103 16 2012 www.pelco.
Installation Instruction 66571764GB3 3. Fire Detection 10 Installation, FX and FXL - control panels The mounting surface must be flat and it must bear the weight of the control panel and the chart file cabinet. The weight of the control panel excl. batteries is 11 kg and incl. batteries (2 x 17 Ah) 23 kg. The weight of the chart file cabinet is 9 kg. The mounting is to be made straight to the wall surface, without any distance bushings or similar, to ensure ingress protection class of IP30.
Installation Instruction 66571764GB3 4. Fire Detection 11 Installation, FXM - control panel The mounting surface must be flat and it must bear the weight of the control panel and the chart file cabinet. The weight of the control panel is exl. batteries is 8 kg and incl. batteries 20 kg. 160 42 The weight of the battery cabinet is exl. batteries is 4 kg and incl. batteries 28 kg. The weight of the chart file cabinet is 9 kg.
Installation Instruction 66571764GB3 5. Fire Detection 12 Installation, FXS - control panel The mounting surface must be flat and it must bear the weight of the control panel and the chart file cabinet. The weight of the control panel is 4.4 kg. The weight of the chart file cabinet is 9 kg. 328 160 40 The mounting is to be made straight to the wall surface, without any distance bushings or similar, to ensure ingress protection class of IP30. 32 FXS control panel © 2009 Schneider Electric.
Installation Instruction 66571764GB3 6. Fire Detection 13 Connecting main power supply Connect the mains supply (230 VAC) There must be a separate fuse (10 A) for the control panel power supply. Cable 3 x 1.5 mm². + ADL - + PO - - IN1 + + PI2 - + PI1 - Note! FXS has not any built-in power supply. The power is fed to the FXS panel from FX or FXM power supply unit using 2 power lines. The power supply PI1 and PI2 inputs in FXS are on the MC2 board.
Installation Instruction 66571764GB3 7. Fire Detection 14 Commissioning 7.1 Necessary devices and documents Devices • A universal measuring instrument (voltage, current, resistance, diode). • A PC and the configuration tool, if the configuration is done when commissioning. Documents • This Installation and Commissioning manual. • Operation manual. • Planning and installation documents for the project. • Client/project configuration data if the configuration is done when commissioning. 7.
Installation Instruction 66571764GB3 8. Preliminary checks 8.1 General Fire Detection 15 The aim of the preliminary checks is to assure that the settings are correct and that the control panel has not suffered any defects during transportation or installation. This is obviously most easy to do when no external cables are connected, except for the necessary power supply connection. 8.2 Preliminary checks PO 2 +24V- PO 1 + BAT T - +24V- 1.
Installation Instruction 66571764GB3 Fire Detection 16 SLC jumper settings 1. Check the following settings: “Prog Update” jumper is not in place. “Dev LED” jumper is in place if you want the detector leds to flash when communicating with the panel or not in place otherwise. Set the right ID. The range is 1…4/panel and is common to SLC, ALC and CLC units. + 14 - CLC jumper settings 1. Check the following settings: Set the right ID. The range is 1…4/panel and is common to SLC ALC and CLC units.
Installation Instruction 66571764GB3 Fire Detection 17 OCA jumper settings 1. Check the following settings: Set the right ID. The range is 1…4/FX and FXL panel. The ID must be different for each IOC and OCA. 9. Control panel test run: Note differences with the FXS! 9.1 Mains connection Note! The panel is in access level 2 when the cover is removed. - BATT + 1. Switch the panel on by connecting the cable between the transformer and the terminal 30VAC on the power supply component board.
Installation Instruction 66571764GB3 9.2 Fire Detection 18 Battery connection PO 2 +24V- PO 1 + BAT T - +24V- 1. Install the batteries in the cabinet. Check that the battery cable is disconnected from the battery terminal BATT. 2. Check battery polarity from the markings on the battery. 3. Connect the battery cables to the poles as follows: The batteries are 12 V batteries. If two batteries are used, they are connected in series.
Installation Instruction 66571764GB3 10. Fire Detection 19 Cable handling and preliminary measurements WARNING! Check by measuring that there is no power in the cables. Cable handling and measurements First disconnect the battery then the mains. 1. Peel off the cable plastic and protective shields. Be careful not to let peeling remains drop onto the component board or between the back wall of the cabinet and the component board. 2.
Installation Instruction 66571764GB3 20 Cable table Cable connection Conductors x area 2 2 x 0.5 mm + Addressable detection shield circuit cables, SLC- loop 2 x 1.0 mm2 + shield 2 2 x 0.5 mm + Addressable detection shield circuit cables, ALC- loop 2 x 1.0 mm2 + shield 2 2 x 0.5 mm + Conventional detection shield circuit cables, CLC- line 2 x 1.
Installation Instruction 66571764GB3 - alarm line Addressable monitor modules, ALC- loop - monitor lines Addressable control modules, ALC- loop - power supply - alarm line Mains supply cable Fire Detection 21 conductor area and length of the power supply cable. Monitor modules EMI- 310, EMI-310+, EMI-311, EMI-311/240, EMI-333, -EMI-410, EMI-410+, EMI-411. Mini monitor modules 55000-833 APO, 55000-832 APO.
Installation Instruction 66571764GB3 11. Addressable detector loops 11.1 Measuring the Cables Fire Detection 22 First disconnect the battery, then the mains Disconnect all power from the control panel. 1. Measure the resistance between the loop wires + and - so that the resistance meter positive (feeding) probe is in the + -conductor. The resistance must exceed 1 kΩ. If the resistance is smaller, locate the cause of the fault and repair it.
Installation Instruction 66571764GB3 11.2 Fire Detection 23 Connecting the loop to the control panel Each FX-SLC and FX–ALCB board has connectors for two loops, FX-ALCA board has only one loop. 1. Check that all power has been disconnected from the control panel. 11.3 Loop 1 B+ A- Loop 1 A+ B+ A+ B- Loop 2 Loop 2 Outgoing end to terminals A+ and A-. Return end to terminals B+ and B- . A- 3. Connect the loop wires to the LOOP terminals of the SLC/ALC board. B- 2.
Installation Instruction 66571764GB3 Fire Detection 24 A short circuit indication is caused by a loop component connected the wrong way or a short circuit in the wires. If short circuit isolators are used, the shorted part of the loop between the closest isolators will be non-operative. By scrolling trough the addresses list for the shorted loop and comparing with the installation plan, the shorted area can be located.
MAINTENANCE 11: (s,c) FAULT 12: (s,c) FAULT 13: (s,c/n) MAINTENANCE 14:(s,c/n) MAINTENANCE 15:(s,c/n) MAINTENANCE 16: (s,c) FAULT 17: (s,c/n) FAULT 18: (s,c/n) MAINTENANCE 19:(s,c/n) FAULT 20: (r) MAINTENANCE 21: (r) FAULT 22: (r) FAULT 51: (r) FAULT 52: (r) FAULT 53: (r) FAULT 54: (r) FAULT 55: (r) FAULT 56: (r) FAULT 57: (r) FAULT 58: (r) MAITENANCE 59: (r) MAINTENANCE 60: (r) MAINTENANCE 61: (r) FAULT 62: (r) FAULT 63: (r) FAULT 64: (r) FAULT 65: (r) FAULT 66: (r) Fire Detection 25 − Siren control
Installation Instruction 66571764GB3 MAINTENANCE 67: (r) MAINTENANCE 68: (r) MAINTENANCE 69: (r) FAULT 70: (r) FAULT 71: (r) FAULT 72: (r) FAULT 73: (r) FAULT 74: (r) FAULT 75: (r) FAULT 76: (r) FAULT 77: (r) FAULT 78: (r) FAULT 79: (r) FAULT 80: (r) FAULT 81: (r) − − − − − − − − − − − − − − − FAULT 82: (r) − FAULT 83: (r) − FAULT 84: (r) FAULT 85: (r,s) FAULT 86: (r) FAULT 87: (?) MAINT 88: (?) MAINT 89: (?) FAULT 90: (r,s) − − − Fire Detection 26 show it as fault warning.
Installation Instruction 66571764GB3 12. Conventional detector lines 12.1 Measuring the Cables Fire Detection 27 1. Disconnect all power from the control panel. 2. Measure the resistance between the wires of the conventional line cable. Set the meter to low voltage resistance measurement (not diode measurement).
Installation Instruction 66571764GB3 12.2 Fire Detection 28 Connection principles 12.2.1 Conventional line Min/max. value of conventional devices internal resistance is depending of detectors threshold voltage and the EOL. Conventional line 4k7 End of line resistance: 4k7, 5% Max. Line resistance: 100 Ω Max load from all detectors in loop: 1.
Installation Instruction 66571764GB3 Fire Detection 29 12.2.2 Input line End of line resistance: 4k7, 5% Max. Line resistance: 100 Ω Alarm resistance: 1k33 – 2k15, 5% (e.g. 4k87 and 2k94 in parallel = 1k833) Line resistance max. 100 Ω CLC 1k33 - 2k15 EOL 4k7 NO Alarm switch Line resistance max. 100 Ω CLC 1k33 - 2k15 EOL 4k7 © 2009 Schneider Electric. All rights reserved.
Installation Instruction 66571764GB3 12.3 Fire Detection 30 Connecting the line to the control panel 12.4 + 2 + 5 + 6 + 9 + 10 + 13 - + 8 + 16 - + 15 - + 12 - + 11 - 3. Connect the pair of wires of the conventional line to the terminals of the CLC board retaining polarity. + 7 - + 4 - Note! The free shielded wire must be as short as possible! + 14 - + 3 - 1. Disconnect all power from the control panel. 2.
Installation Instruction 66571764GB3 12.5 Fire Detection 31 Compatible detectors and manual call points Compatibility of detectors with the CLC conventional line is determined by the following factors: - Supply voltage range - Current consumption in standby condition - Voltage across the detector in alarm condition - Series resistance (either in the detector or in the base) - End-Of-Line resistor The voltage supplied by the CLC to the conventional line is 21 Vdc to 24 Vdc.
Installation Instruction 66571764GB3 Fire Detection 13. Monitored output lines 13.1 Measuring the cables and connecting the end-of-line resistors 1. Disconnect all power from the control panel. 2. Measure the resistance between the monitored output line cable wires so that the resistance meter positive (feeding) measuring end is in the “–“ wire of the line. The resistance meter must indicate a break. If the resistance meter indicates a resistance value, the cause of the fault must be located.
Installation Instruction 66571764GB3 13.2 Fire Detection 33 Connecting the monitored output lines to the control panel The FX-MC board has one monitored output line connector. Note! If the ‘Side CPU not in use’- jumper is NOT in place in the MC2 (system assistant processor is in use), then in the case of the MC2 system fault the system assistant processor controls the CO1 output as a fire router output regardless of the configuration. 13.
Installation Instruction 66571764GB3 14. Control outputs 14.1 Clean relay outputs Fire Detection 34 The FX-MC2 board has three clean contact outputs. Each FX-IOC board has two clean contact outputs. Each FX-OCA board has 16 clean contact outputs. The function of the outputs is defined with the configuration tool.
Installation Instruction 66571764GB3 35 Note! The max. current consumption of the FX - control panel (with PSB- power supply board), all loops and addresses and all control panel outputs is 1 A in standby condition and 4.5 A in alarm condition. The standby time required for the system may limit the max. load of the outputs.
Installation Instruction 66571764GB3 15. Signal inputs 15.1 Connecting the inputs to the control panel Fire Detection 36 The FX-MC2 board has two clean contact input connectors. Each FX-IOC board has four clean contact input connectors.
Installation Instruction 66571764GB3 16. Info-line devices / connections 16.1 INFO-fault messages Text at display fault in info port X comm.
Installation Instruction 66571764GB3 16.3 Fire Detection 38 DAPX Picture 2. Connection between FX-panel and DAPX REPX and REPX-OB © 2009 Schneider Electric. All rights reserved. 16.4 Picture 3. Connection between FX-panel and REPX Note! If REPX-OB is installed in FX: rack, only INFO line needs to be connected. Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Document Number 66571764GB3 Telephone: +358 10 446 511 Fax: +358 10 446 5103 16 2012 www.pelco.
Installation Instruction 66571764GB3 16.5 Fire Detection 39 MCOX and MCOX-OB Picture 4. Connection between FX-panel and MCOX Note! If MCOX-OB is installed in FX: rack, only INFO line needs to be connected 16.6 CODI / Codinet © 2009 Schneider Electric. All rights reserved. There are two versions of CODIs: CODI and CODINET. Only CODINET may be used in panel communications (19200bd). CODI is only up to 9600bd.
Installation Instruction 66571764GB3 17. Fire Detection 40 Configuration Note! The panel is set to the configuration mode with configuration tool. This can be done also with the following procedure. CURRENT ACCESS LEVEL:2 CHANGE TO ACCESS LEVEL 3:0000 CURRENT ACCESS LEVEL: 3 CONFIGUARTION STARTED READY FOR CONFIGURATION © 2009 Schneider Electric. All rights reserved. Set control panel to access level 3. 1. Select with “MENU”-button from main menu. 2. Press the wheel. 3.
Installation Instruction 66571764GB3 18. Fire Detection 41 Serial communication ports RS485 Gnd - + SY S 1 Gnd - + SYS 2 Gnd - + NOTE! Only one of these ports can be connected at a time. RS232 Tx Rx Gnd RS232 and RS485 serial communication ports using INFO protocol are on the top of the FX-MC2 board. These ports are isolated. FX panel can communicate with INFO devices such as FMPX, MCOX etc. via these ports. Also a printer using serial communication can be connected to either of these ports.
Installation Instruction 66571764GB3 18.1 Fire Detection 42 FX 3NET communication network FX_ FRE “Seeing” = Communication cable - one twisted pair - shielded Building 1 Fire Routing Building 2 FX_ FX_ “Seeing” “Seeing” S1 S1 S2 S1 S2 “Visible” FX_ S1 S2 S1 S2 “Visible” S1 S2 “Visible” FX_ FX_ “Visible” FX_ System 1(S1) and System 2 (S2) = serial communication line Picture 5.
Installation Instruction 66571764GB3 18.3 N 5 FxNet FxNet 2 .... FxNet … FxNet SAB 1 43 Modem connections in the communication network 1 SYSTEM Fire Detection SAB SYSTEM SYSTEM 2 1 1 2 SYSTEM SYSTEM 1 2 SAB SYSTEM SYSTEM 2 1 Group of Fx-panels X … FxNet SAB SAB SYSTEM SYSTEM 6 .... Fiber Modem SAB 1 2 23 ....
Installation Instruction 66571764GB3 Fire Detection 19. Alarm routing equipment 19.1 Connecting the alarm routing equipment to the control panel 44 The alarm routing equipment must not be connected until all other necessary commissioning procedures have been performed.
Installation Instruction 66571764GB3 20. FX, FXL and FXM connections 20.
Installation Instruction 66571764GB3 20.
Installation Instruction 66571764GB3 20.
Installation Instruction 66571764GB3 20.
Installation Instruction 66571764GB3 20.
Installation Instruction 66571764GB3 20.
Installation Instruction 66571764GB3 51 Connectors on the MC2 board Terminal name PI 1 PI 2 PO MO Connector symbol 24 V 24 V + 24 V 24 V + 24 V 24 V + + CO 1 CO 2 CO 3 + IN 1 - Purpose Description Power supply 1 in (-) Power supply 1 in (+) Power supply 2 in (-) Power supply 2 in (+) Power supply out (-) Power supply out (+) Monitored output line (-) Monitored output line (+) Relay output 1 NC Relay output 1 C Relay output 1 NO Relay output 2 NO Relay output 2 C Relay output 2 NC Relay output 3
Installation Instruction 66571764GB3 Connectors on the PSA and PSB - board Terminal name Connector symbol Purpose Description 30 VAC 30 VAC input from transformer. + 24 V 24 V + 24 V 24 V + BATT PO 1 PO 2 20.9 52 Battery Battery + Power supply 1 out Power supply 1 out + Power supply 2 out Power supply 2 out + Connection for the standby battery. Power supply output 1 for external load. Power supply output 2 for external load.
Installation Instruction 66571764GB3 20.
Installation Instruction 66571764GB3 20.
Installation Instruction 66571764GB3 20.13 55 Connectors on each ALCA- board Terminal name PO 1 LOOP 1 20.14 Fire Detection Connector symbol 24 V 24 V + BB+ AA+ Purpose Description Power supply out (-) Power supply out (+) Return end Return end + Outgoing end Outgoing end + Power output for loop devices in loop 1 that require external power supply. Intellia loop devices.
Installation Instruction 66571764GB3 20.15 Fire Detection 56 Connectors on FMPX, DAPX, REPX and REPX-OB- board and MCOX and MCOX-OB- board Terminal name Isolated serial port for rd 3 part external devices RS232 RS485 RS485 Line IN RS232 Line OUT RS485 Power input 1 PI 1 Description rd For 3 part devices. Ie. integration to BMS. Configuration / input port. Panel connection must be disconnected during configuration. For PELCO devices using INFO- protocol. Note! Both inputs must be connected.
Installation Instruction 66571764GB3 20.16 CO1 (D9-connector) TE3 TE2 TE1 57 Connectors on CODINET modem adapter Terminal name TE4 Fire Detection Connector symbol 2:RxD (in) 3:TxD (out) 4:DTR (out) 5:ISO GND 6:DSR (in) 7:RTS (out) NC DSR RxD TxD ISO GND DTS DTR +24 V GND T/R+ T/RR+ RISO GND Mounted J2 Mounted (default) Not mounted Description RS232-line. Power input. (Isolated) RS485-line. Terminating resistor of 120 ohm between ±T/R. Normally not used. RS485 2-wires, ±T/R.
Installation Instruction 66571764GB3 Fire Detection 58 0832 Pelco Finland Oy P.O. Box 415, 02601 Espoo Finland For FX 0832-CPD-1082 Issue 4 For FXL 0832-CPD-1083 Issue 3 For FXM 0832-CPD-1084 Issue 3 EN 54-2:1997/AC:1999/A1:2006 EN 54-4:1997/AC:1999/A1:2002/A2:2006 Options: 7.8; 7.9.1; 7.10.3; 7.11; 7.12.2; 7.13; 8.3; 8.4; 8.9; 9.