Instruction manual

ConneXium Ethernet Switch 499NES18100 8-Port 10/100 Base-TX Quick Reference Guide
12 31005416 02 August 2004
Interfaces,
Displays and
Controls
Accessories
Stability vibration IEC 60068-2-6 Test FC, testing level in
line with IEC 61131-2 E2 CDV
Germanischer Lloyd Guidelines for the
Performance of Type Tests Part 1
shock IEC 60068-2-27 Test Ea, testing level in
line with IEC 61131-2 E2 CDV
Interfaces eight TP/TX ports RJ45 sockets, 10/100 MBit/s
indicator contact 1 A maximum, 24 V
Displays equipment status
LEDs
1 green P1 – power 1, supply voltage 1 present
1 green P2 – power 2, supply voltage 2 present
1 red FAULT – indicator contact is open and
indicates error
port status LEDs 8 green/yellow DAT/STAT 1 ... 8 – data/link status
Controls eight-pole DIP switch LA1 ... LA8 – suppress messages about
link status
Scope of delivery order number:
499NES18100
ConneXium rail switch module
terminal block for supply voltage
installation and operating instructions
TF Ethernet SFTP CAT5 RJ45 cables 490NTW000**
TF Ethernet SFTP CAT5 RJ45 crossed cables 490NTC000**
where ** = length in meters; allowable choices are 2, 5, 12, 40 or 80.
Printed in France

02
Visit http://www.schneider-electric.com for your nearest Schneider Electric affiliate.