Specifications
8
Presentation
Advantys STB
Distributed I/O Solution 1
Network Interface Modules
The STB Npp 2212 network interface modules, located at the beginning of each
island, are gateways for exchanging data between the network or bus master PLC
and the Advantys STB automation island.
They also enable (except Economy CANopen NIM module) the configuration of
parameters and addressing of installation devices. These settings are stored in the
module’s internal RAM or Flash memory. Optionally, they can be saved to the
STB XMP 4440 removable memory card (32 Kb).
1 Fieldbus master
2 External
c 24 V power supply
3 HMI terminal
4 Network Interface Module “NIM”
5 Power Distribution Module “PDM”
6 I/O modules
7 Other network nodes
8 Other slave PLCs
9 Bus terminator
The Advantys STB offer comprises 8 network interface modules, each one dedicated
to a specific network or bus:
Network interface modules are powered by an external
c 24 V power supply. They
convert this power to
c 5 V to provide logic power to the Advantys STB I/O modules.
Logic power for the I/O modules in each extension segment is provided by that
segment’s “BOS” STB XBE 1200 module. See page 5.
This built-in 5 V power supply provides up to 1.2 A current.
Presentation
Network or bus Network interface module
Ethernet network STB NIP 2212
CANopen Bus STB NCO 2212, STB NCO 1113
Modbus Plus Network STB NMP 2212
Fipio Bus STB NFP 2212
INTERBUS Bus STB NIB 2212
Profibus DP Bus STB NDP 2212
DeviceNet Network STB NDN 2212
3
1
8
7
9
2
4
5
6
Power Supply for Network Interface Module
C
haracteristics:
p
age 10
References:
pages 11 to 13
Dimensions:
page 13