Specifications

6
Selection guide
Advantys STB
Distributed I/O Solution 1
Network Interface Modules
(1) One Advantys STB island corresponds to 1 device on the bus or the network.
(2)Any I/O module inserted after the Economy CANopen NIM is treated as an individual device
by the bus master.
Applications Data exchange between master PLC and Advantys STB I/O modules
Bus or network type Ethernet TCP/IP network CANopen Bus
Bus or network nature Industrial LAN CAN field bus
Structure Physical interface 10 BASE-T ISO 1198
Access method CSMA-CD CSMA-MA, multimaster
Baud rate 10 Mbit/s 10 Kbit/s…1 Mbit/s depending
on bus length
10 Kbit/s…800 Mbit/s
depending on bus length
Medium Shielded dual twisted pair via
Ethernet ConneXium cabling
system
Shielded dual twisted pair
Configuration Number of devices
(1)
max. 256 per segment,
unlimited with switches
127 slaves
Maximum length 500 m according to 802.3
standard
1,000 m with conneXium
cabling system
From 30 m (1 Mbit/s) to
5,000 m (10 Kbit/s)
From 50 m (800 Kbit/s) to
5,000 m (10 Kbit/s)
Network interface module
features
Number of I/O modules per
Advantys STB island (1)
max. 32 with:
- 1 primary segment
- max. 6 extension segments
max. 20 per Economy
CANopen NIM (2)
Power supply voltage c 24 V not isolated (19.2…30 V)
Logic power supply Provides c 5 V logic power to all the I/O modules of an island (1200 mA)
Services used - Embedded Web
(configuration, diagnostics,
and access to variables)
- TCP/IP Modbus
- SNMP agent
- Process Data Object (PDO)
- Service Data Object (SDO)
- Special function Object
- Network management (NMT)
- PDO mapping
Type of module
STB NIP 2212 STB NCO 2212 STB NCO 1113
Pages 11