Specifications
4
Description (continued)
Advantys STB
Distributed I/O Solution 1
Open and Modular System
The island bus can support:
b Preferred modules of type ATV 38/58 controller (available later). This type of
preferred module is installed between two segments.
b Standard CANopen devices. They are installed at the end of the island with up to
12 standard CANopen devices. These devices may reduce the maximum island
length to 6.5 m (baud rate dependant).
The island bus comprises:
1 STB N
pp: Network Interface Module “NIM”.
2 STB PDT 3100:
c 24 V Power Distribution Module “PDM”. It is installed
immediately to the right of the “NIM” and provides
c 24 V power to the I/O
modules requiring DC power.
3 STB EHC 3020: 1 channel counter module.
4 STB EPI 1145: module for Tego Power motor-starters.
5 STB AV
p and STB ACp: analog I/O modules
6 STB EPI 2145: module for TeSys model U starter-controllers.
7 STB XBE 1000: EOS bus extension module: It is always installed in the slot the
farthest to the right in the primary or extension segment, and is used to extend the
island bus to another segment.
8 ATV 58 controller: preferred module with special option card (available at a later
date).
9 STB XBE 1200: EOS bus extension module. It is installed at the beginning of the
extension segment.
10STB XBE 2100: CANopen extension module (max. 12 devices per island).
11FTB 1CN: Advantys FTB IP 67 monobloc I/O splitter boxes.
12FTX DPTL12: CANopen bus line terminator (with 120 Ω resistance).
13STB XCA 100
p: island bus extension cables.
14User supplied cable.
(1) Includes the preferred modules and the standard CANopen devices.
Description (continued)
Advantys STB with application-specific modules, preferred module, and
standard CANopen devices
1 2 23 13 86 7 10 11 1
2
1495 54 413
max. 6.50 m with max. 15 I/O modules (1)
P
resentation:
p
age 2
References:
page 5
Dimensions:
page 5