Specifications

30
Characteristics (continued)
Advantys STB
Distributed I/O Solution 1
Analog Input/Output Modules
Characteristics of STB ART 0200 analog input module
Thermocouple range B E J K R S T
Temperature unit
° C or ° F (° C by default)
Nominal values
° C 130…1820 - 270…
+1000
- 200…
+ 760
- 270…
+ 1370
- 50…
+ 1665
- 50…
+ 1665
- 270…
+ 400
° F 266…3200 - 328…
+1832
- 328…
+ 1400
- 454…
+ 2498
- 58…
+ 3029
- 58…
+ 3029
- 328…
+ 752
Data resolution
Increments of 0.1 ° C or ° F
Broken wire detection
Monitored independently on each channel
Typical conversion times With internal cold-junction
compensation
ms 230 @ 50 Hz
210 @ 60 Hz
With external cold-junction
compensation
ms 400 @ 50 Hz
360 @ 60 Hz
Accuracy (thermocouple errors not included)
° C ± 10.5 ± 7 ± 10.5 ± 7
° C ± 7 @
25 ° C
± 5 @ 25 ° C ± 7 @ 25 ° C ± 5 @
25 ° C
° F ± 51 ± 44.6 ± 51 ± 44.6
° F ± 44.6 @
77 ° F
± 41 @ 77 ° F ± 44.6 @ 77 ° F ± 41 @
77 ° F
Temperature probe range Pt 100 Pt 1000 Ni 100 Ni 1000 Cu 10
Type
2, 3 or 4-wire (3-wire by default)
Temperature unit
° C or ° F (° C by default)
Nominal values IEC
° C - 200…+ 850 (by default) - 60…+ 180 - 100…+
260
° F - 328…+ 1562 (by default) - 76…+ 356 - 148…+
500
US/JIS
° C - 100…+ 450 N/A
° F - 148…+ 842 N/A
Data resolution
Increments of 0.1 ° C or ° F
Broken wire detection
Monitored independently on each channel
Max. wiring resistance 4-wire
50 (IEC/US/JIS) 500 (IEC/US/JIS) 50 500 50
2 or 3-wire
20 (IEC/US/JIS) 200 (IEC/US/JIS) 20 200 20
Typical conversion times 3-wire
ms 340 @ 50 Hz
300 @ 60 Hz
2 or 4-wire
ms 200 @ 50 Hz
180 @ 60 Hz
Accuracy (“RTD” errors not
included)
@ 25 ° C
° C ± 1 ± 1 ± 4
@ 60 ° C
° C ± 2 ± 1 ± 4
@ 77 ° F
° F ± 1.6 ± 1.6 ± 6
@ 140 ° F
° F ± 3.6 ± 1,6 ± 6
mV range
Range of the scale
mV ± 80 (- 81.92…+ 81.92)
Data resolution
Increments of 0.01 mV
Typical conversion times
ms 170 @ 50 Hz
150 @ 60 Hz
Input impedance
M 10 typical
Accuracy @ 25 ° C/77 ° F
± 0.1 % of full scale @ ambient temperature
@ 60 ° C/140 ° F
± 0.15 % of full scale @ ambient temperature
P
resentation:
p
age 28
Description:
page 28
References:
page 31
Dimensions:
page 31
Wiring: