Specifications
20
Characteristics (continued)
Advantys STB
Distributed I/O Solution 1
Digital Input/Output Modules
Characteristics of digital output modules
Type of output module STB DDO 3200 STB DDO 3230 STB DDO 3410 STB DDO 3600 STB DAO 8210
Number of output channels
2 2 4 6 2
Output nominal
values
Voltage
V 24 DC 24 DC 24 DC 24 DC 115/230 AC
Current/channel
A 0.5 2 0.5 2 @ 30° C (86° F)
1 @ 60° C (140° F)
Output logical Source –
Output voltage
values
Permanent voltage
V 19.2…30 DC 20...265 AC
Absolute maximum voltage
V 56 DC for 1.3 ms, decaying voltage pulse 300 AC for 10 s
400 AC for
1 cycle
Response time Off-to-on
620 µs @ 0.5 A
load
520 µs 560 µs @ 0.5 A
load
715 µs @ 0.5 A
load
10.0 ms
On-to-off
575 µs @ 0.5 A
load
720 µs 870 µs @ 0.5 A
load
955 µs @ 0.5 A
load
10.5 ms
Hot swapping supported
Yes
Reverse polarity protection against miswired power
Yes
Isolation voltage Field-to-bus
V 1500 DC for 1 minute 1780 AC for
1minute
Channel-to-channel
V – 500 DC for
1minute
–
Output protection
(internal)
Electronic overcurrent protection (OCP) Transient voltage
via Varistor and
RC
On-state
leakage/channel
mA 0.4 @ 30 VDC
max.
1.0 @ 30 VDC
max.
0.4 @ 30 VDC max. 2.5 @ 230 VAC
2.0 @ 115 VAC
Maximum surge current
A 5 @ 500 µs
(no more than
six/minute)
10 @ 500 µs
(no more than
six/minute)
5 @ 500 µs
(no more than six/minute)
30 (1 cycle)
20 (2 cycles)
Maximum load Capacitance
µF 50 –
Inductance
0.5 H @ 4 Hz switch frequency
L = 0.5/I
2
x F (1)
–
Minimum load current
mA 0.5 2 0.5 5
Short circuit Electronic protection
Per group (2 channels per group) –
Feedback
Per channel 2 per channel, 4 or 6 per group
(2 channels per group)
–
Fault recovery
response
Default setting
Channel latched off - requires user reset No fault detection
User-configurable setting (2)
Auto-recovery or latched off
Fallback modes Default
Predefined fallback values on both channels
User-configurable setting (2)
Hold last value, predefined fallback values on one or more channels
Fallback states
(when predefined is
the fallback mode)
Default
Both channels to 0
User-configurable setting (2)
Each channel configurable to 1 or 0
Output polarity Default
Logic normal on both channels
User-configurable setting (2)
Logic normal or reverse configurable by channel
I/O base
STB XBA 1000 STB XBA 2000
Power Distribution
Module “PDM”
requirements
Voltage
V 24 DC Either 115 AC or
230 AC
Model
STB PDT 3100 STB PDT 2100
Power protection
10 A time-lag fuse
on the “PDM”
(3) 10 A time-lag fuse on the “PDM”
Logic bus current consumption @ 5 VDC
mA 60 80 90 70
(1) L = load inductance (H), I = load current (A), F = switching freq. (Hz).
(2) Requires the Advantys configuration software.
(3) Recommended user-supplied 2,5 A time-lag fuses on each channel.
P
resentation:
p
age 18
Description:
page 18
References:
page 22
Dimensions:
page 23
Wiring: