Specifications

19
Characteristics
Advantys STB
Distributed I/O Solution 1
Digital Input/Output Modules
Characteristics of digital input modules
Type of input module STB DDI 3230 STB DDI 3420 STB DDI 3610 STB DAI 5230 STB DAI 7220
Number of input channels
2 4 6 2
Input nominal values Voltage
V 24 DC 24 DC 24 DC 115 AC
(50/60 Hz)
230 AC
(50/60 Hz)
Input Logic
Sink Sink Sink
Type (IEC/EN 61131-2)
Type 2 Type 1+ Type 1 Type 1 Type 1
Input response time On-to-off
ms 0.625 @ 0.2 input
filter time
1.35 @ 0.5 input
filter time
1.74 1.5 line cycles
Off-to-on
ms 0.610 @ 0.2 input
filter time
0.925 @ 0.5 input
filter time
1.21 1.5 line cycles
Input limit values Frequency
Hz 47…63
At state 1 Voltage
V 11…30 DC 15…30 DC 74…132 AC 159…256 AC
Current
mA 6 min. 2.5 min. 2 min. 4 min.
At state 0 Voltage
V - 3…5 DC 0…20 AC 0…40 AC
Current
mA 2 max. 1.2 max. 0.5 max. 2 max.
Input voltage values Permanent voltage
V 30 DC 132 AC 265 AC
Absolute maximum voltage
V 56 DC for 1.3 ms, decaying pulse 200 AC for
1 cycle
400 AC for
1 cycle
Hot swapping supported
Yes
Reverse polarity protection against miswired power
Yes
Isolation voltage Field-to-bus
V 1500 DC for 1 minute 1780 AC for 1 minute
Channel-to-channel
V
Input protection
Resistor-limited
Current supplied to
field device
Electronic short-circuit protection
(SCP)
mA 100 per channel 60 max.
Input filtering Default setting
ms 1.0 1.0 1.0 max.
User-configurable setting (1)
ms 0.20
0.50
1.0
2.0
4.0
8.0
16.0
0.50
1.0
2.0
4.0
8.0
16.0
Tolerance
ms ± 0.1 ± 0.25
Input polarity Default setting
Logic normal on both channels
User-configurable setting (1)
Logic normal or reversed, configurable by channel
I/O base
STB XBA 1000 STB XBA 2000
Power Distribution
Module “PDM”
requirements
Voltage
V 24 DC 115/230 AC
Model
STB PDT 3100 STB PDT 2100
Power protection
5 A time-lag fuse on the “PDM”
Logic bus current consumption @ 5 VDC
mA 50 60 70 50
(1) Requires the Advantys configuration software.
P
resentation:
p
age 18
Description:
page 18
References:
page 22
Dimensions:
page 23
Wiring: