Specifications
17
1
Output modules
For direct current (transistor) For alternating current (triac) For direct/alternating current (relay)
24 VDC 115/230 VAC 24 VDC
115/230 VAC
2 4 6 2 2 form C (N.O/N.C)
relay outputs
2 form A/B relay
outputs
Source – –
– – –
0.5 A 2.0 A 0.5 A 2 A @ 30 °C (86°F)
1 A @ 60 °C (140°F)
2 A per contact 7 A per contact
620 µs @ 0.5 A
load
520 µs 560 µs @ 0.5 A
load
715 µs @ 0.5 A
load
10.0 ms 5.25 ms 10 ms
575 µs @ 0.5 A
load
720 µs 870 µs @ 0.5 A
load
955 µs @ 0.5 A
load
10.5 ms 6.75 ms 10 ms
– – – – – – –
Two connectors (6-point): screw-type STB XTS 1100 or
spring-type STB XTS 2100
Two connectors (5-point): screw-type STB XTS 1110 or
spring-type STB XTS 2110
STB XBA 1000 STB XBA 2000 STB XBA 3000
24 VDC 115/230 VAC 24 VDC (coil)
STB PDT 3100 STB PDT 2100 STB PDT 3100
1500 VDC for 1 minute 1780 VAC for 1 minute 1780 VAC for 1 minute
– 500 VDC for
1minute
– – 500 VAC for 1 minute
Yes
Yes (2) (3) Yes, 10 A time-lag fuse on the Power Distribution Module “PDM”
Electronic overcurrent protection (OCP) – –
STB DDO
3200
STB DDO
3230
STB DDO
3410
STB DDO
3600
STB DAO
8210
STB DRC
3210
STB DRA
3290
22
(2) Yes, 10 A time-lag fuse on the Power Distribution Module “PDM”.