Specifications

14
Presentation,
description,
characteristics
Advantys STB
Distributed I/O Solution 1
Power Distribution Modules
The STB PDT p100 Power Distribution Modules “PDM” provide power for the I/O
module sensors and actuators via the sensor bus 1 and the actuator bus 2.
Two power distribution modules are available for the Advantys STB distributed I/O:
b The STB PDT 3100 module is dedicated to providing power to the I/O module sensors
and actuators requiring a
c 24 V power supply
b The STB PDT 2100 module is dedicated to providing power to the I/O module sensors
and actuators requiring a
c 115/230 V power supply.
The Advantys STB PDT
p100 power distribution modules comprise:
1 A location for a customizable label.
2 A status block with 2 display LEDs:
IN LED on: the sensor bus power supply is present,
OUT LED on: the actuator bus power supply is present.
3 A color-coded module identification stripe (red for
a 115/230 V, blue for c 24 V).
4 A connector for removable screw-type connector (STB XTS 1130) or spring-type
connector (STB XTS 2130) used to connect the sensor power supply.
5 A connector for removable screw-type connector (STB XTS 1130) or spring-type
connector (STB XTS 2130) used to connect the actuator power supply.
To be ordered separately:
6 A STB XBA 2200 mounting base, width 18.4 mm.
This base features:
7 A location for a customizable label.
8 A captive grounding screw.
.
Presentation
Choice of Power Distribution Module “PDT” determined by I/O modules
Power
distribution
module
Voltage
(V)
STB I/O modules
Digital Analog Applica-
tion-
specific
Inputs Outputs Relay
Outputs
Inputs Outputs
STB PDT 3100 c 24 DDI 3230 DDO 3200 DRC 3210 AVI 1270 AVO 1250 EPI 1145
DDI 3420 DDO 3230 DRA 3290 ACI 1230 ACO 1210 EPI 2145
DDI 3610 DDO 3410 ART 0200 EHC 3020
DDO 3600
STB PDT 2100 a 115 DAI 5230 DAO 8210
a 230 DAI 7220 DAO 8210
c 24 V
IN
OUT
IN
OUT
a
115/230 V
a
115/230 V
a 115/230 V
11
22
Description
7
2
3
4
5
6
8
1
Characteristics
Module Type STB PDT 3100 STB PDT 2100
Power supply voltage
V c 24 (1) a 115/230
Max. current For inputs
A 4 at 30 °C
2.5 at 60 °C
5 at 30 °C
2.5 at 60 °C
For outputs
A 8 at 30 °C
5 at 60 °C
10 at 30 °C
5 at 60 °C
Sensor/actuator bus voltage range
V c 19.2...30 (2) a 85...265 (3)
Plug in/plug out with power on
No
Nominal consumption
mA 0 on c 5 V logic power supply
Reverse polarity protection
Yes, on the actuator bus
Built-in overcurrent protection For inputs
By 5 A time-delayed fuse
For outputs
By 10 A time-delayed fuse
Max. current on the grounding terminal
A 30 for 2 minutes
Voltage-detect thresholds IN/OUT LED turns on
u c 15 V ± 1 V > a 70 V ± 5 V
IN/OUT LED turns off
< c 15 V ± 1 V < a 50 V ± 5 V
Mounting base
STB XBA 2200 width 18.4 mm
(1) Use a
c
24 V external power supply with very low safe allowable voltage.
(2) DC power supplies may be shared or separate, or shared with the
c
24 V SELV power supply of the network interface module.
(3) AC power supplies for a given distribution module from a three-phase transformer must be connected at the same phase.
R
eferences:
p
age 15
Dimensions:
page 15