Distributed I/O Advantys STB 09-03 Distributed I/O Advantys STB The open device integration I/O system ART. 061231 www.schneider-electric.
Contents Advantys STB Distributed I/O Solution 1 Open and modular system b Presentation, description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 2 to 4 b References, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5 Network interface modules Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 6 and 7 b Presentation, description, characteristics . . . . . . . . . . . . . . . . . .
Advantys STB Distributed I/O Solution Presentation, composition Open and Modular System Presentation To meet the needs of machine manufacturers and users, automation architectures have been decentralized while delivering performance comparable to centralized systems. The Advantys STB distributed I/O system, an open, modular input/output system, makes it possible to design islands of automation managed by a master controller via a bus or communication network.
Advantys STB Distributed I/O Solution Description 1 Open and Modular System Description Advantys STB: primary segment 1 2 3 4 5 6 In the example above, the primary segment comprises: 1 STB Npp: Network Interface Module “NIM”. It is placed at the beginning of the primary segment. Each island must have one NIM module only. 2 STB PDT 2100: Power Distribution Module “PDM”. It is installed immediately to the right of the NIM and provides a 115/230 V power to the I/O modules requiring AC power.
Description (continued) Advantys STB Distributed I/O Solution 1 Open and Modular System Description (continued) Advantys STB with application-specific modules, preferred module, and standard CANopen devices 1 2 3 4 5 6 7 13 8 13 9 2 4 5 10 14 11 12 max. 6.50 m with max. 15 I/O modules (1) The island bus can support: b Preferred modules of type ATV 38/58 controller (available later). This type of preferred module is installed between two segments. b Standard CANopen devices.
Advantys STB Distributed I/O Solution References, dimensions 1 Open and Modular System References Description Reference Network Interface Modules (Includes the island bus terminator) PDM Power Distribution Modules Digital I/O modules Analog I/O modules Parallel interfaces Tego Power applications TeSys Model U applications Counter module Description Use See page 10 See page 15 See page 22 See page 30 See page 35 See page 37 See page 41 Reference EOS bus extension module STB XBE 1000 STB XBE 1200 I
Selection guide Advantys STB Distributed I/O Solution Network Interface Modules Applications Data exchange between master PLC and Advantys STB I/O modules Bus or network type Ethernet TCP/IP network CANopen Bus Bus or network nature Industrial LAN CAN field bus Physical interface 10 BASE-T ISO 1198 Access method CSMA-CD CSMA-MA, multimaster Baud rate 10 Mbit/s 10 Kbit/s…1 Mbit/s depending 10 Kbit/s…800 Mbit/s on bus length depending on bus length Shielded dual twisted pair via Ethernet Co
1 Modbus Plus Network Fipio Bus INTERBUS Bus Profibus DP Bus Industrial LAN compliant with the Modbus Plus standard Open industrial field bus INTERBUS industrial field bus Industrial field bus compliant with the FIP standard (Generation 4) (Profibus DP V.O) Modbus Plus standard FIP standard Token passing DeviceNet Network RS 485 Network compliant with v.2.0 of the Open DeviceNet Vendor Assoc.
Advantys STB Distributed I/O Solution Presentation 1 Network Interface Modules Presentation The STB Npp 2212 network interface modules, located at the beginning of each island, are gateways for exchanging data between the network or bus master PLC and the Advantys STB automation island. They also enable (except Economy CANopen NIM module) the configuration of parameters and addressing of installation devices. These settings are stored in the module’s internal RAM or Flash memory.
Advantys STB Distributed I/O Solution Description 1 Network Interface Modules Description Network interface modules (except for the INTERBUS STB NIB 2212 module) They feature the following on the front panel: 1 4 5 2 6 3 1 A connector used to connect the island to the fieldbus. See the various connector types on page 9. 2 Two rotary node addressing selectors on the bus or the network.
Advantys STB Distributed I/O Solution Characteristics 1 Network Interface Modules Characteristics Type of network interface module STB NIP 2212 NCO 2212 NCO 1113 NMP 2212 CANopen Economy CANopen Modbus Plus Fipio Network or bus Ethernet Compliance with bus or network standards IEEE 802.3 CIA DS-301 Power supply voltage cV 24 not isolated Input current mA 700 Voltage limits cV 19.2…30 Output voltage to the island logic bus cV 5.25 ± 0.21 Output current rating A 1.
Advantys STB Distributed I/O Solution References 1 Network Interface Modules Network Interface Modules Description STB NIP 2212 STB NCO 2212/1113 Reference Ethernet network Power supply voltage c 24 V CANopen Bus c 24 V STB NCO 2212 0;135 CANopen Bus (Economy NIM) c 24 V STB NCO 1113 0;130 Modbus Plus network c 24 V STB NMP 2212 0.145 Fipio Bus c 24 V STB NFP 2212 0.145 INTERBUS Bus c 24 V STB NIB 2212 0.155 Profibus DP Bus c 24 V STB NDP 2212 0.
References (continued) Advantys STB Distributed I/O Solution 1 Network Interface Modules Connection accessories Ethernet Network Description Fitted at both ends Length Straight shielded 2 RJ45 connectors to connect 2 m twisted pair cable data terminal equipment (DTE) for connecting 5m hubs and switches 490 NTW 000 pp 12 m 40 m 80 m Reference 490 NTW 000 02 (1) 490 NTW 000 05 (1) 490 NTW 00012 (1) 490 NTW 000 40 (1) 490 NTW 000 80 (1) Weight kg – – – – – CANopen Bus Description Junction box Use
References (continued), dimensions Advantys STB Distributed I/O Solution 1 Network Interface Modules Connection accessories (continued) INTERBUS Bus Description Use Length Reference Prefitted cables to connect 2 network interface modules “NIM” 0.
Advantys STB Distributed I/O Solution Presentation, description, characteristics Power Distribution Modules a 115/230 V a 115/230 V 1 IN 1 IN 2 OUT c 24 V 1 2 OUT Presentation The STB PDT p100 Power Distribution Modules “PDM” provide power for the I/O module sensors and actuators via the sensor bus 1 and the actuator bus 2.
Advantys STB Distributed I/O Solution References, dimensions 1 Power Distribution Modules References Power distribution modules Power Supply Type Voltage Reference c 24 V STB PDT 3100 Weight kg 0.130 a 115/230 V STB PDT 2100 0.129 Separate parts Description Use for Mounting base (width 18.4 mm) Removable connectors STB XBA 2200 STB PDT 3100 Keying pins Sold in lot of 1 Mounting of STB PDT p100 power supply modules on DIN rails Screw-type 10 STB XBA 2200 Weight kg 0.
Selection guide Advantys STB Distributed I/O Solution 1 Digital Input/Output Modules Configuration Input modules For direct current For alternating current Voltage 24 VDC 115 VAC Number of channels 2 4 6 2 Sink Type 2 Type 1+ Type 1 – Type 1 Input Logic Type (IEC/EN 61131-2) 230 VAC Load current/channel (outputs) – Response time 610 µs @ 0.2 ms input filter time 625 µs @ 0.2 ms input filter time 925 µs @ 0.5 ms input filter time 1.35 ms @ 0.5 ms input filter time 1.21 ms 1.
1 Output modules For direct current (transistor) For alternating current (triac) For direct/alternating current (relay) 24 VDC 115/230 VAC 24 VDC 115/230 VAC 2 2 form C (N.O/N.C) relay outputs – – – – 0.5 A 2 A @ 30 °C (86°F) 1 A @ 60 °C (140°F) 2 A per contact 7 A per contact 620 µs @ 0.5 A 520 µs load 560 µs @ 0.5 A 715 µs @ 0.5 A load load 10.0 ms 5.25 ms 10 ms 575 µs @ 0.5 A 720 µs load 870 µs @ 0.5 A 955 µs @ 0.5 A load load 10.5 ms 6.
Advantys STB Distributed I/O Solution Presentation, description Digital Input/Output Modules Presentation The STB digital input/output modules consist of input modules, output modules, and relay output modules. The digital I/O offering is defined as follows: b 5 digital input modules: v one 2-channel module, one 4-channel module, and one 6-channel module with 24 VDC voltage, v one 2-channel module with 115 VAC voltage, v one 2-channel module with 230 VAC voltage.
Advantys STB Distributed I/O Solution Characteristics 1 Digital Input/Output Modules Characteristics of digital input modules Type of input module Number of input channels STB DDI 3230 2 STB DDI 3420 4 STB DDI 3610 6 STB DAI 5230 2 STB DAI 7220 24 DC 24 DC 24 DC Logic Sink Sink Sink 115 AC (50/60 Hz) – 230 AC (50/60 Hz) – Type (IEC/EN 61131-2) Type 2 Type 1+ Type 1 Type 1 Type 1 1.35 @ 0.5 input 1.74 filter time 0.925 @ 0.5 input 1.
Advantys STB Distributed I/O Solution Characteristics (continued) 1 Digital Input/Output Modules Characteristics of digital output modules Type of output module Number of output channels Output nominal values STB DDO 3200 2 STB DDO 3230 2 STB DDO 3410 4 STB DDO 3600 6 STB DAO 8210 2 24 DC 115/230 AC Voltage V 24 DC 24 DC 24 DC Current/channel A 0.5 2 0.5 Output logical Source Output voltage values Permanent voltage Absolute maximum voltage Response time Off-to-on V V 19.
Advantys STB Distributed I/O Solution Characteristics (continued) 1 Digital Input/Output Modules Characteristics of relay Type of relay module Number of relay output channels Output nominal values V STB DRC 3210 STB DRA 3290 2 relay outputs (form C, NO/NC contact pairs) 2 relay outputs (form A/B, NO/NC contact pairs) 24 DC, 115/230 AC 24 VDC A 2 7 230 VAC A 2 7 V 5…30 DC V 20…250 AC Off-to-on ms 5.25 10 On-to-off ms 6.
Advantys STB Distributed I/O Solution References 1 Digital Input/Output Modules References Digital input modules Input voltage Modularity (No. of channels) 2 (sink) Type 2 STB DDI 3230 0.110 4 (sink) Type 1+ STB DDI 342 0.111 6 (sink) Type 1 STB DDI 3610 0.112 115 VAC 2 Type 1 STB DAI 5230 0.120 230 VAC 2 Type 1 STB DAI 7220 0.122 Compliance Reference IEC/EN 61131-2 0.5 A Modularity (No. of channels) 2 (source) Yes STB DDO 3200 0.112 2A 2 (source) Yes STB DDO 3230 0.
Advantys STB Distributed I/O Solution Dimensions, wiring 1 Digital Input/Output Modules Dimensions STB DDI/DDO 3pp0 Side view STB DAI ppp0/DAO 8210 STB DRC 3210/DRA 3290 STB DRA 3290 70 (2) A A A B B B 128,3 35 42 (1) 13,9 75,5 28,1 18,4 95 (1) STB XBA 1000/2000/3000 I/O bases (2) STB XTS 11p0/21p0 connectors Wiring Digital input modules STB DDI 3230 STB DDI 3420 STB DDI 3610 A A 1 2 3 4 5 6 + Sensor 1 IN – + Sensor 1 – + Sensor 2 – IN IN 1 2 3 4 5 6 STB DAI 5230 + Sen
Advantys STB Distributed I/O Solution Wiring (continued) 1 Digital Input/Output Modules Wiring (continued) Digital output modules for direct current STB DDO 3200 0.5 A A 1 2 3 4 5 6 + Actuator 1 – B 1 2 3 4 5 6 Actuator 2 – STB DDO 3230 Two field actuators receiving field power from external 24 VDC power supply instead of the PDM 2.
Advantys STB Distributed I/O Solution Wiring (continued) 1 Digital Input/Output Modules Wiring (continued) Digital output modules for alternative current STB DAO 8210 A 0.
Selection guide Advantys STB Distributed I/O Solution 1 Analog Input/Output Modules Configuration Analog input modules For voltage For current Number of channels 2 inputs Range - 10…+ 10 V 0…20 mA Resolution 11 bits + sign 12 bits Load current/channel (outputs) – Response time 5.
1 Analog output modules For multirange analog For voltage For current 2 outputs Thermocouple B, E, J, K, R, S et T “RTD” Pt 100, Pt 1000, Ni 100, Ni 1000, Cu 10 ± 80 mV Voltage (- 0…+ 10 V, - 10…+ 10 V) Current (0…20 mA) 15 bits + sign 11 bits + sign or 12 bits 12 bits 5 mA 20 mA – 3.
Advantys STB Distributed I/O Solution Presentation, description Analog Input/Output Modules Presentation The STB analog inputs allow the acquisition of various analog values encountered in industrial applications.The STB analog outputs are used to control analog field devices such as variable speed drives, proportional control values, etc.
Advantys STB Distributed I/O Solution Characteristics 1 Analog Input/Output Modules Characteristics of analog input modules Type of input module Number of input channels STB AVI 1270 2 single-ended analog input channels STB ACI 1230 2 single-ended analog input channels Range ± 10 V 0…20 mA Resolution Maximum input (without damage) Response time Hot swapping supported Return data format Update time Input filter Integral linearity Differential linearity Input impedance Current supplied to field devi
Advantys STB Distributed I/O Solution Characteristics (continued) 1 Analog Input/Output Modules Characteristics of STB ART 0200 analog input module Thermocouple range Temperature unit Nominal values Data resolution B E J ° C or ° F (° C by default) 130…1820 - 270… - 200… + 1000 + 760 266…3200 - 328… - 328… + 1832 + 1400 Increments of 0.
Advantys STB Distributed I/O Solution References, dimensions 1 Analog Input/Output Modules References Analog input modules Input current ± 10 V 0…20 mA Thermocouple, “RTD”, ± 80 mV Modularity (No. of channel) 2 2 2 Compliance Reference IEC/EN 61131-2 Yes Yes Yes STB AVI 1270 STB ACI 1230 STB ART 0200 Weight kg 0.115 0.116 – Analog output modules Output current Modularity (No.
Advantys STB Distributed I/O Solution Wiring 1 Analog Input/Output Modules Wiring Analog input/output modules STB AVI 1270 Two isolated analog sensors 24 VDC from island sensor bus to power analog field devices A 1 2 3 4 5 6 + U Sensor 1 – + U Sensor 2 – 1 2 3 4 5 6 + U Sensor 1 – 0V B 1 2 3 4 5 6 A c 24 V B c 24 V 1 2 3 4 5 6 + U Sensor 2 – 0V + – 24 VDC STB ACI 1230 Two isolated analog sensors A 1 2 3 4 5 6 + Sensor 1 I – 1 2 3 4 5 6 + I – I Sensor 1 – 0V + I – 0V Wirin
Wiring (continued) Advantys STB Distributed I/O Solution 1 Analog Input/Output Modules Wiring (continued) STB AVO 1250 Two isolated analog actuators 24 VDC from island actuator bus-to-power analog field devices A 1 2 3 4 5 6 Actuator 1 + U – Actuator 1 – 0V + U – B c 24 V 1 2 3 4 5 6 1 2 3 4 5 6 + U B Actuator 2 A c 24 V Actuator 2 1 2 3 4 5 6 + U – 0V + – 24 VDC STB ACO 1210 Two isolated analog actuators 24 VDC from island actuator bus-to-power analog field devices A A 1 2 3 4
Advantys STB Distributed I/O Solution Presentation, description, dimensions Parallel Interface for Tego Power Applications Presentation The STB EPI 1145 parallel interface is a component of the Advantys STB island designed for the remote connection of 8 motor-starters (or 4 motor-starters in both directions). These TeSys model d motor-starters use the Tego Power installation assistance system.
Advantys STB Distributed I/O Solution Characteristics, references 1 Parallel Interface for Tego Power Applications Characteristics Electrical characteristics Module Type Plug in/plug out with power on Connection P/S Protection Consumption On c 5 V logic bus On c 24 V sensor bus On c 24 V actuator bus mA mA mA STB EPI 1145 Yes Via 1 HE 10 connector (30 contacts). Via STB PDT 3100 c 24 V power distribution module Via STB PDT 3100 power distribution module fuse 130 max. 100 max.
Advantys STB Distributed I/O Solution Presentation, description, dimensions Parallel Interface for TeSys Model U Applications Presentation 1 The STB EPI 2145 1 parallel interface is a component of the Advantys STB distributed I/O system designed for the remote connection of 4 TeSys model U starter-controllers (12 inputs and 8 outputs).
Advantys STB Distributed I/O Solution Characteristics, references 1 Parallel Interface for TeSys Model U Applications Characteristics Module Type Hot swapping Connection Power Supply Protection Consumption On c 5 V logic bus On c 24 V sensor bus On c 24 V actuator bus mA mA mA STB EPI 2145 Yes Via 4 RJ45 connectors Via STB PDT 3100 c 24 V power distribution module Via STB PDT 3100 power distribution module fuse 130 max. 100 max. 50 (with all 8 outputs at 0 state), max.
Advantys STB Distributed I/O Solution Presentation, description 1 Counter Module Presentation Counting parts or events, grouping objects, controlling incoming and outgoing data streams, and measuring lengths or positions all require counting functions. The STB EHC 3020 counter module performs these functions for an Advantys STB automation island (controlled by a master connected to the island) with a max. counting frequency of 40 kHz.
Characteristics Advantys STB Distributed I/O Solution 1 Counter Module Functional characteristics Configurable functions Number 1 of the 6 configurable functions (using the Advantys configuration software) Frequency meter This function measures the frequency received on the IN A input. This frequency is always expressed in Hz (number of pulses per second), with a precision of 1 hertz. Also measures the speed in Units per second.
Advantys STB Distributed I/O Solution Characteristics (continued) 1 Counter Module Characteristics Electrical characteristics Module Type Frequency on counting inputs kHz STB EHC 3020 1 channel max. 40 Hot swapping supported Yes Mounting base STB XBA 3000 PDM Power distribution module required Voltage provided V Reference 24 STB PDT 3100 Consumption on the logic c 5 V mA bus Isolation Between island bus and I/O c V 60 typical, 140 max.
Advantys STB Distributed I/O Solution References, dimensions, wiring 1 Counter Module References Description Counter module 1 channel 40 kHz Input type Reference 2/3 wire c 24 V detectors Incremental encoder c 24 V Mechanical contacts STB EHC 3020 Weight kg – Sold in Reference lots of 1 STB XBA 3000 Weight kg 0,048 Separate Parts Description Use for Base 28.
Advantys STB Distributed I/O Solution Presentation 1 Configuration Software Presentation The configuration process of the Advantys STB system includes the following steps: b If necessary, configure all the I/O modules for Advantys STB (digital, analog, and application-specific), and the modules with a default configuration. b Configure the reflex functions handled at the island level. These settings are defined using the STB SPU 1000 dedicated Advantys configuration software.
Advantys STB Distributed I/O Solution Functions 1 Configuration Software Functions Module Editor The number of tabs provided by the editor is determined by the mode in which you execute the Advantys Configuration Software (Local or Online). The editor displays some or all of the following tabs: General, etc. “General”Tab This read-only tab (island online or offline), provides general information and displays the key technical characteristics of the selected module. CANopen bus interface NIM module.
Functions (continued) Advantys STB Distributed I/O Solution Configuration Software Functions (continued) “I/O Image” Tab This tab, accessible when the island is online, provides a table with data concerning the: b Input/Output modules comprising the Advantys STB island (values and state of each module). b Operator Terminal connected to the network interface module.
Functions (continued), references Advantys STB Distributed I/O Solution 1 Configuration Software Functions (continued) Reflex Editor For applications requiring short response times (< 3 ms), the Advantys Configuration Software allows you to create reflex functions that work directly on the island output modules, thereby freeing the bus master from parsing and process them. These reflex functions can be associated with “priority” I/O modules to ensure the reliability of the response time.
Advantys STB Distributed I/O Solution Presentation 1 Phaseo Regulated Power Supplies ABL 7 power supplies The ABL-7 range of power supplies is designed to provide the d.c. voltage necessary for the control circuits of automation system equipment. Split into three families, this range meets all the needs encountered in industrial, commercial and residential applications.
Presentation (continued) Advantys STB Distributed I/O Solution 1 Phaseo Regulated Power Supplies Using c 24 V b Using c 24 V enables so-called protection installations (PELV) to be built. Using PELV is a measure designed to protect people from direct and indirect contact. Measures relating to these installations are defined in publication NF C 12-201 and in standard IEC 364-4-41.
Advantys STB Distributed I/O Solution Selection 1 Phaseo Regulated Power Supplies Selection of power supplies The characteristics to be taken into account when selecting a power supply are: b the required output voltage and current, b the mains voltage available in the installation. This may however result in several products being selected as suitable. Other selection criteria must therefore be taken into account.
Advantys STB Distributed I/O Solution Characteristics 1 Phaseo Regulated Power Supplies Technical characteristics Type of power supply Approvals Conforming to Safty standards EMC Low frequency harmonic currents ABL 7RE UL, CSA, TÜV, CTick UL 508, CSA 22.
Advantys STB Distributed I/O Solution Characteristics (continued) 1 Phaseo Regulated Power Supplies Derating The ambient temperature is a determining factor which limits the power that an electronic power supply can deliver continuously. If the temperature around the electronic components is too high, their life will be significantly reduced. Conversely, a power supply can deliver more than its nominal power if the ambient temperature remains largely below the rated operating temperature.
Advantys STB Distributed I/O Solution Selection, references, dimensions 1 Phaseo Regulated Power Supplies ABL 7RE and ABL 7RP power supply: protection of the power supply line a 115 V single-phase Thermal-magnetic circuit-breaker GB2 C60N Type of mains supply Type of protection GB2 pB07 MG24517 (1) GB2 pB07 MG24517 (1) GB2 pB08 MG24518 (1) GB2 pB12 MG17454 (1) GB2 pB07 MG24517 (1) GB2 pB07 MG24517 (1) GB2 pB09 MG24519 (1) (1) Disjoncteur certifié UL.
Advantys STB Distributed I/O Solution 1 Automation Product Certifications Product certifications and marine classification authorities In some countries, certification of certain electrical components is enforced by law. A standard conformity certificate is then issued by the official organization. Each certified product must carry approval symbols when enforced.
Advantys STB Distributed I/O Solution 1 Automation Product Certifications Product certifications and marine classification authorities (continued) Sociétés de classification des navires Normal execution Certified ABS BV DNV GL GOST LR RINA RRS Pending certification USA France Norway Germany CEI United-Kingdo m Italy CIS ABE-7 99155-96HH Advantys STB Lexium MHD/BPH Magelis IPC Magelis TXBT-F Magelis XBT-F/FC Magelis XBT-H/P/E/HM/PM Micro 45016846A001 A7961 99086-96HH 97/00114 ELE/
Power Requirements worksheet Advantys STB Distributed I/O Solution 1 Power Requirements The c 5 V required for the logic power supply of the I/O modules is provided by the modules: v Network Interface NIM positionned at the beginning of the primary segment. v BOS bus extension module positionned at the beginning of the extension segment. This built-in 5 V power supply provides up to 1200 mA current.
Advantys STB Distributed I/O Solution 1 Community Regulations and Protective Treatment Community regulations European Directives The opening of European markets implies a harmonization of regulations in the various European Union member states. European Directives are documents used to remove obstacles to the free movement of goods and their application is compulsory in all states of the European Union.
Product Reference Index 1 170 BNO 671 00 170 MCI 007 00 170 MCI 020 10 170 MCI 020 36 170 MCI 020 80 170 MCI 021 20 170 MCI 100 00 170 XTS 020 00 4 490 NAD 911 03 490 NAD 911 04 490 NAD 911 05 490 NTW 000 02 13 13 12 12 12 12 13 12 490 NTW 000 12 490 NTW 000 40 490 NTW 000 80 490 NTW 00012 13 13 13 12 and 37 12 and 37 37 12 12 12 9 990 NAD 211 10 990 NAD 211 30 990 NAD 230 00 990 NAD 230 10 12 12 12 12 A ABL 7RE2402 ABL 7RE2403 ABL 7RE2405 ABL 7RE2410 ABL 7RP2403 ABL 7RP2405 ABL 7RP2410 APP 2R2E APP
Distributed I/O Advantys STB 09-03 Distributed I/O Advantys STB The open device integration I/O system ART. 061231 www.schneider-electric.