The following table provides an overview of how the ATV31 behaves depending on the
different configuration methods:
Parameters configured
by…
…Advantys …PowerSuite,
...control keys
…both
ATV31 restart
Advantys PowerSuite Advantys
Island restart
Advantys PowerSuite Advantys
Island & ATV31 restart
Advantys PowerSuite Advantys
CANopen bus error
Advantys PowerSuite Advantys
IO scanning/PLC error
Advantys PowerSuite Advantys
Misconfigura-
tions on the
CANopen
extension
Below is a description of how the bus behaves in the event of potential
misconfigurations, particularly addressing errors:
Error Description
Duplicate bus address The two devices with the duplicate address are excluded
from bus operation and no data can be exchanged with
them. Data exchange with all the other devices continues
as normal and is unaffected by this fault.
Device has the same
address as
XBE 2100
If a device on the bus has the same address as the XBE
2100 extension module, the bus will fail to start and no data
will be exchanged.
Note:
In both cases, the relevant diagnostic message will be displayed in the Advantys
software or on the island head Web page to enable the error to be detected on startup.