Quick start manual
Premium and Advantys STB on Profibus DP.doc – Juni-05
Schneider Electric
27
Configuring
CANopen
communication
1
The transfer rate for the
CANopen extension must be
set to 500 kbps via the “Baud
Rate Tuning” menu item. This
transfer rate matches that set
for the ATV31 and
FTB modules.
Adjusting the
device
parameters
1
It is possible to specify parameters for the individual devices on the CANopen
extension, which are transferred to the devices every time the bus is restarted. This
means, for example, that all the ATV31 parameters
(with the exception of the communication settings) can also be specified here
instead of in the PowerSuite software.
2
Double-click on the device to
open the parameter window.
This screenshot shows the
ramp settings for the ATV31
by way of an example. New
values can be specified by
entering them in the “User
defined label” field.
Note: In the case of the
example project, no values
need to be changed here.
WARNING!
Using Advantys for parameterizing the ATV31 conflicts with parameterization via the
PowerSuite software/manual entry via the operator panel and vice versa, i.e., the last set
of parameters written to the ATV31 is always valid. Consequently, only one
parameterization method should be used for the ATV31 (see “ATV31 variable speed
drive”).
Note:
The parameterization can also be used to activate other I/O channels on the
Advantys FTB.