Quick start manual

Premium and Advantys STB on Profibus DP.doc – Juni-05
Schneider Electric
21
Advantys FTB
Specifying the
address and
transfer rate
The CANopen address and transfer rate are set manually on the modules via rotary
switches. There are two rotary switches for the address and one for the transfer rate. In
the example software, both FTB modules are configured with the addresses 31 and 32
and the transfer rate is set to
500.0 kbits.
Element Function
1 Transfer rate
2 Address 10x
3 Address 1x
Rotary switch position Transfer rate
0 Autom. recognition
1 10 kbps
2 20 kbps
3 50 kbps
4 100 kbps
5 125 kbps
6 250 kbps
7 500 kbps
8 800 kbps
9 1 Mbps
Overview of
addresses
In the example software, the individual devices on the extension have the following
addresses:
Device Address Comment
XBE 2100 26 Calculated automatically by the Advantys software
ATV31 (1) 27 Set via operator panel
ATV31 (2) 28 Set via operator panel
ATV31 (3) 29 Set via operator panel
ATV31 (4) 30 Set via operator panel
FTB 1CN08E08SPO 31 Set via rotary switches
FTB 1CN12E04SPO 32 Set via rotary switches