Quick start manual
Premium and Advantys STB on Profibus DP.doc – Juni-05
Schneider Electric
20
CANopen extension
Introduction
The address and transfer rate must be specified for all the devices on the CANopen
extension.
Note: It is important to ensure that the addresses run consecutively in descending order,
starting with 32, which is the maximum start address. The maximum start address can
be set anywhere within the range 8-32 using the Advantys software (see “Advantys
STB” chapter). Again, this should be taken into account when assigning addresses.
ATV31
Specifying the
address and
transfer rate
(manually)
1
The CANopen address and
transfer rate are set manually
via the control buttons on the
device.
2
First, use the control buttons to
select the “Communication”
submenu.
In the “Communication” menu,
the CANopen address must be
set in the “AdC0" parameter. In
the example software provided,
the values 27 to 30 have been
set aside for the four drives on
the drive island.
3
In the “Communication” menu,
you must also set the transfer
rate in the "BdC0" parameter to
the value 500.0 (kbits).
Note:
Alternatively, the address and transfer rate can also be parameterized using the
PowerSuite configuration software.