Installation guide

Commissioning
890USE17100 September 2003 91
Do Not Hot Swap
Modules with
Different Model
Numbers
If an I/O module is removed from its base and then replaced by a module with a
different model number, the remaining modules on the island will continue to operate
but the new module will not be operational. The green RDY LED on the new module
will blink to indicate that it is in pre-operational mode, and an LED on the NIM will
indicate that a device mismatch has been detected.
If you choose to keep the module with a different model number in the base, you will
have to reconfigure the system to make it operational.
Do Not Reset the
Island Bus while
a Module is
Removed
If you push the RST button on the NIM while an I/O module is missing from the island
bus, the island will re-configure, and only the modules to the left of the missing one
will be operational.
For example, if an I/O module is removed from address location 4 of the island bus
as shown below:
and then the RST button on the NIM is pushed, the modules in locations 1, 2 and 3
will remain operational, and the modules to the right of the empty location will not be
detected.
The green RDY LED on the modules in address locations 5 and 6 will flash to
indicate that they are in pre-operational mode.
123 56
X
4
123 XX
X
5
6
4
RST