Installation guide

Commissioning
88
890USE17100 September 2003
Hot Swapping Advantys STB Modules
Module Insertion
and Removal
The assembled base units on a DIN rail together with a NIM form the island bus.
Advantys STB modules can then be inserted into and removed from these base
units to complete or adjust the physical design.
Maximum
Insertion/
removal Cycles
The base units are designed to withstand up to 50 module insertion/removal cycles.
Note: If any of your modules are being used to provide operating power to a large
inductive load (at or near a maximum of 0.5 H), make sure that you turn any field
devices OFF before removing the field power connector from the modules. The
output channel on the modules may be damaged if you remove the connector while
the field devices are ON.
Note: If modules are inserted and removed from a base more than 50 times, the
integrity of the module-to-base contacts cannot be guaranteed. Be sure the history
of your modules is known before hot swapping them.