Power Isolation Requirements on the Island Bus
Isolation
Requirements
The power source for the NIM, and any BOS modules on the extension segments,
must be galvanically isolated. Isolation is not provided by the NIM or BOS modules
themselves.
External Power
Supply
Requirement
Any external 24 VDC power supply that provides the source power to the island bus
must be SELV-rated. The input side must be galvanically isolated from the output
side.
This SELV requirement applies to all 24 VDC power supplies supporting both logic
power and field power—i.e., supplies that provide 24 VDC to the NIM or to an
STB PDT 3100 power distribution module.
CAUTION
IMPROPER GALVANIC ISOLATION
The power components are not galvanically isolated. They are intended
for use only in systems designed to provide SELV isolation between the
supply inputs or outputs and the load devices or system power bus. You
must use SELV-rated supplies to provide 24 VDC source power to the
island
Failure to follow this precaution can result in injury or equipment
damage.