Installation guide
Site Requirements
24
890USE17100 September 2003
Environmental
Requirements
This equipment meets agency certification for UL, CSA, CE and FM class 1 div 2.
This equipment is intended for use in a Pollution Degree 2 industrial environment, in
over-voltage Category II applications (as defined in IEC publication 60664-1), at
altitudes up to 2000 m (6500 ft) without derating.
Parameter Specification
protection ref. EN61131-2 IP20, class 1
agency ref. EN61131-2 UL 508, CSA 1010-1, FM Class 1 Div. 2,
CE
isolation voltage ref. EN61131-2 2000 VDC field-to-bus for 24 VDC
3250 VDC field-to-bus for 115/230 VAC
Note: No internal isolation voltage; isolation requirements must
be met by using SELV-based external power supply.
over-voltage class ref. EN61131-2 category II
operating temperature 0 ... 60° C (32 ... 140° F)
storage temperature -40 ... +85° C (-40 ... +185° F)
operating humidity 95% relative humidity @ 60° C (noncondensing)
nonoperating humidity 95% relative humidity @ 85° C (noncondensing)
supply voltage variation,
interruption, shut-down and
start-up
IEC 61000-4-11
damped oscillatory wave IEC 61000-4-12
sinusoidal vibration 5 ... 20 Hz with 6.35 mmDA
20 ... 500 Hz with 5 g
shock ref. IEC88, part 2-27 30 g half sine
operating altitude 2000 m (2187 yd)
transport altitude 3000 m (3281 yd)
free-fall ref. EN61131-2 1 m (1.09 yd)